background image

Installation, Operation and Service Instructions

INSTRUCTION MANUAL 310952B

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER’S USE.

NOTE: This product is not intended for use in potable water applications.

WARNING: California Proposition 65 Warning! This product contains chemicals known

to the State of California to cause cancer and birth defects or other reproductive harm.

 SAFETY

 INSTRUCTION
This safety alert symbol will be used in this manual to 
draw attention to safety related instructions. When used, 
the safety alert symbol means ATTENTION! BECOME 

ALERT! YOUR SAFETY IS INVOLVED! FAILURE TO 

FOLLOW THE INSTRUCTIONS MAY RESULT IN A 

SAFETY HAZARD.

OPERATIONAL LIMITS

Circuit Sentry 

Flo-Setter

Maximum Limitations

Pressure (PSI)             Temperature °F

NPT

300

250

DESCRIPTION
Bell & Gossett Circuit Sentry

TM

 Flo-Setter Balance & 

Commissioning Valves are precision engineered valves 
used in heating and cooling systems for the distribution 
of flow in various sections of the system. The dynamic 
balancing and commissioning valve ensures easy and 
reliable balancing of the system, regardless of any 
fluctuations in the differential pressure of the system. 
The Bell & Gossett Circuit Sentry

  

Flo-Setter limits the 

maximum flow in the system and can be used in both 
variable and constant flow systems. The clear scale on the 
lockable handle ensures that flow setting is simple and 
user friendly while the integral P/T ports allow verification 
of pressure.

INSTALLATION INSTRUCTIONS
Circuit Sentry

  

Flo-Setter Balance & Commissioning 

Valves are uni-directional valves and can be installed in 
most altitudes; however, they should be installed in a 
position to facilitate the ease of balancing the system. Be 
sure to install the Circuit Sentry

 

 Flo-Setter with the arrow 

pointing in the direction of flow.

CIRCUIT BALANCE VALVES 

WITH NPT CONNECTIONS
Apply pipe compound conservatively to male  
connecting fittings only.

CAUTION: The use of Teflon impregnated 

pipe compound and Teflon tape on 

threads provides lubricity. Care should 

be taken to prevent over tightening of the valves 

which may damage the Circuit Sentry Flo-Setter.

Check connections for leaks.

OPERATION INSTRUCTIONS
HOW TO USE BELL & GOSSETT CIRCUIT SENTRY  

FLO-SETTER  BALANCE & COMMISSIONING VALVES 

FOR PRE-SET FLOW BALANCING
The Circuit Sentry Flo-Setter Balance & Commissioning 
Valve is easily set, and the pre-setting is read on the 
scale. The flow rate of the valve can be determined from 
the flow rate graphs for the valve dimension in question. 
See the flow rate graphs of the valve in the FLOW CURVE 
BOOK (G10092) or Submittal (A-609.22 or A-611) for 
further information about the adjustment setting.
Select the appropriate size Circuit Sentry Flo-Setter 
Balance & Commissioning Valve (normally line size) for 
the required GPM.
Please note: The scale is for the adjustment of flow. If you 
want to close the branch line, use an isolation ball valve 
in conjunction with the Circuit Sentry Flo-Setter.
The handle can be locked after adjustment. Remove the 
B&G logo cap and tighten with 5mm hexagonal key.

HOW TO USE BELL & GOSSETT CIRCUIT SENTRY FLO-

SETTER TO PROPORTIONAL BALANCE A SYSTEM
The system is easily balanced by adjusting the pump 
according to the required differential pressure across the 
critical valve.
When the differential pressure is available the system will 
automatically be balanced.