background image

Laser Printer

                      INTRODUCTION

                    

Thank you for purchasing a Belkin Uninterruptible Power
Supply (UPS). Each year, several natural and man made

occurrences put the power supplied to your electronics in
your home or office in jeopardy. At risk are your hardware,
software and data because of these power problems.

            IMPORTANT SAFETY INSTRUCTIONS

              

Please save this manual!

It contains important operating instructions and warranty
information pertaining to your UPS.

Please save or recycle the packaging materials!

The UPS packaging was designed with great care to

provide protection during shipment and delivery.  These
materials are invaluable if you ever have to return the UPS
for service. Damage sustained during transit is not covered

under the warranty.

Federal Communications Commission Interference

Statement

This equipment has been tested and found to comply with

the limits for a Class B digital device, pursuant to Part 15 of
the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a

residential installation. This equipment generates, uses and
can radiate radio frequency energy and, if not installed and
used in accordance with the instructions, may cause

harmful interference to radio communications. To assure
continued compliance, use only shielded interface cables
when connecting to computer or peripheral devices. Any

changes or modifications not expressly approved by the
party responsible for compliance could void the user’s
authority to operate this equipment.

             UPS FEATURES AND FUNCTIONS

 

Your UPS features 3 LED indicators which specific’s certain
functions on your UPS. Please review the Front Panel
diagram and with this chart, as it will assist you in the use of
your UPS.

 Indicator

Condition

Meaning

_ Solid Green

AC Power is on

ON LINE

(Green LED)

_ Flashing Green

AVR is active

ON BATTERY

(Yellow LED)

_ Flashing Yellow

LED with Audible

Alarm (Beeping)

This condition for the On-
Battery LED can indicate 1 of 2
problems:

1. The UPS is on battery

backup and an intermittent

audible alarm is on. The

UPS will begin shutdown

procedure.

2. Battery is low. The UPS will

start shutdown. The buzzer
sounds an audible alarm.

_

 Solid Red

The Fault/Overload can
indicate 1 of 2 problems.

1. There is a problem with

the UPS. The LED will be
lit continuously, and the
unit will sound an audible
alarm for 10 seconds.

2. Battery is weak or bad;

the battery needs to be
replaced.

FAULT/

*OVERLOAD/

*Replace

Battery

(Red Led)

_ Flashing Red

Battery output is drawing
more power than the UPS
can provide.

SITE WIRING

FAULT

(ON REAR PANEL

)

_

 Solid Red

There is either no ground
circuit or a reversed polarity
in the building wiring.

           BATTERY REPLACEMENT PROCEDURE

Replacement requires removing the battery cover plate on

the front of the UPS. No tools are needed. To replace the

batteries:

1.  Press fastener to remove the battery cover plate on

the front of the UPS (Fig. 1 & 2).

2.  Disconnect the insulated connectors from the battery

terminals (Fig. 3 & 4).

3.  Remove the battery then insert a new battery pack,

and push the connectors onto the battery terminals

(black to black & red to red) (Fig. 3 & 4).

NOTE: 

There may be a small spark at the battery

terminals when reconnecting the connectors. This is

normal and will not harm you or the UPS.

4.  Close the battery cover (Fig. 1).

USERS MANUAL

BELKIN TOWER-RACK SERIES UPS

F6C1000-TW-RK
F6C1250-TW-RK
F6C1500-TW-RK

                               ALARMS

                     

BATTERY BACK UP (Slow Alarm)

When in the UPS is in battery BACK-UP mode, the On Battery
(Yellow LED) illuminates and the UPS sounds an audible alarm.
The alarm stops when the UPS returns to normal ON LINE
operation.

LOW BATTERY (Rapid Alarm)

When the UPS is in battery BACK-UP mode and the battery energy
begins to run low, the UPS will beep rapidly until it shuts down from
a depleted battery or returns to ON LINE normal operation.

OVERLOAD (Continuous alarm)

When the UPS is overloaded (the connected loads exceed the
maximum rated capacity), the UPS emits a continuous alarm to
warn of an overload condition. Disconnect nonessential equipment.
from the UPS to eliminate the overload.

FAULT (10 Seconds Continuously)

When the UPS occur fault, the UPS emits a 10 seconds continuous
alarm to warn of a fault condition. Disconnect the equipment from
the UPS prior to checking the equipment.

To Silence Audible Alarm

While in battery BACK-UP mode, push on/off/test button less than
1.5 seconds to silence the audible alarm. (This does not work if the
UPS is under LOW BATTERY or OVERLOAD condition.

                            REAR PANEL

   

       

A

_

  BATTERY BACK UP SURGE PROTECTION OUTLETS

Only data sensitive equipment such as a computer, monitor
and external drive should be plugged into these outlets.
Battery power is automatically provided in case of a power
outage. Power (AC or battery) is not supplied to these outlets
when the UPS is switched off. (Do not plug surge protectors or
power strips into the battery back up outlets).

Note!  During the AVR Mode, the total load that you will be
placing on the battery back up outlets should not exceed
80% of the unit’s capacity.

B

_

  PHONE/FAX/ MODEM PROTECTION

The phone/fax/modem lines are surge protected and provide
complete safety for line connection.

C

_

  INTERFACE PORTS (USB & RS232)

The UPS provides both a USB and RS232 port for use with
your computer. 

NOTE: Choose one port only.

D

_

  AC INPUT BREAKER (CIRCUIT BREAKER)

The circuit breaker button will be triggered if an overload
condition forces the UPS to disconnect itself from utility power.
If the button sticks out, disconnect nonessential equipment and
depress breaker.

E

_

  AC INPUT POWER CORD

F

_

  SITE WIRING FAULT INDICATOR

The Site Wiring Fault LED will illuminate when one of the
following conditions exist:
1. 

Open or high-resistance ground

2. 

Hot and neutral polarity reversal

3. 

Overloaded neutral circuit

G

_

  NETWORK PROTECTION

This connector is used for protecting the transmission line of
Ethernet card from surge, noise and spike.

H

_

  ACCESSORY SLOT

Optional SNMP Slot

                         CONTENTS

  

You should have received the following:
1 – UPS unit

1 – Bulldog Plus Shutdown Software
1 – USB Cable
1 – Serial Cable

1 – Phone Line Cable

                           INSTALLATION

                                              

Note!

Before installation, please inspect the UPS Upon
receipt. Make sure that the UPS is not damaged.

Connect to AC Utility Power

Connect the AC inlet to utility power via the power
cord. Check whether the Site Wiring Fault indicator
is lit or not. If so, please check the utility wiring.

Charging the Battery

For best results, charge the battery for 8 hours prior to initial
use. The UPS charges its battery whenever it is connected to
the utility power.

Plug in Power Devices

Plug your devices into the AC outlets on the rear of the UPS.
To use the UPS as a master on/off switch, make sure all of
the loads are switched on.

Caution: Never connect a laser printer or
scanner to the backup outlets of UPS with
other computer equipment. A laser printer

or scanner draws significantly more power
when in use than when idle. This may
overload the UPS.

Turning on the UPS

Turn on your UPS by pressing and holding the On/Off/Test

button for approximately 2 seconds until the “ON LINE” Green
comes on.

Turning off the UPS

Turn off the UPS by pressing and holding the On/Off/Test
button for more than 2 seconds until the “ON LINE” or “ON
BATTERY” LED goes off.

To Conduct a Self Test

Use the self-test to verify both the operation of the UPS and
the condition of the battery. In normal utility power, push the

On/Off/Test button less than 1.5 seconds and the UPS
performs a self-test function. During the self-test, the UPS
operates in back-up mode.

Note! During the self-test, the UPS briefly operates on-
battery backup power (the on-battery LED comes on). If
the UPS passes the self -test, it returns to on-line

operation. If the UPS fails the self-test, it immediately
returns to on-line operation and lights the replace battery
LED. The loads are not affected. Recharge the battery

overnight and perform the self- test again. If the replace
battery LED is still on, the battery will need to be
replaced.

Connect the phone/ fax/ modem/ lines

Connect a single phone/ fax/ modem line into the surge-
protected sockets on the back of the UPS. The RJ-11
modular sockets accepts standard single line telephone
connections. The connection will require another length of
telephone cable, which is supplied.

Note! 

This connection is optional but highly suggested as

phone/ fax/modem lines often carry dangerous surges and
spikes. The UPS works properly without a phone/ fax/ modem
connection.

Caution! 

The phone/ fax/modem protection feature could be

rendered inoperable if improperly installed. Make sure that
the telephone line from the wall is plugged into the connector
marked “IN”, and the device to be protected is plugged into
the connector marked “ OUT”.

Connect the Network Protection Lines

Connect the network line from the wall to the connector
marked “IN”, then connect the device (Ethernet card) to be
protected to the connector marked “OUT”.

* All equipment must be turned off prior to hardware
installation.

                 SYSTEM REQUIREMENTS

       

    

The UPS can be used without the software and can be used
with any computer using a monitor or a flat panel screen.

Also, you do not have to have the software installed to utilize
the battery backup outlets.

To fully utilize the UPS and its software, your computer must

be able to operate the following operating systems: 95/ 98/

ME/ NT4/ 2000/ 2003/ XP & Linux & Higher and have a Serial

or USB port.

              SERIAL OR USB COMMUNICATION PORT
                (INSTALLATION OPTIONAL)

To fully utilize the Bulldog Plus Shutdown Software; you will

need to connect the UPS to your computer.
The communication port will provide the following features:
1.  Monitoring charger status
2.  Monitoring UPS status
3.  Monitoring battery status and condition
4.  Monitoring the utility status
5.  Use the ON/OFF/TEST UPS power switch function to

schedule UPS for power saving

REAR PANEL 

   fig. 2

A

B

C

E

D

F

G

H

 

Fig. 1

Fig. 2

Fig. 3

for Model: F6C1500-TW-RK

Fig. 4

for Model: F6C1000-TW-RK
                 F6C1250-TW-RK

ON/ OFF/ TEST

ON BATTERY

ON LINE

FAULT/
 * OVERLOAD/
 * REPLACE BATTERY

FRONT PANEL 

   fig. 1

Отзывы: