UK24BAC
Belimo Gateway MP to BACnet MS/TP
16 / 20
UK24BAC • en • v1.9 • 06.2018 • Subject to changes
www.belimo.com
Version overview
Firmware V1.10
New functions/modifications:
The disengaged gear is represented on the objects ACT_VALUE_[n] and ABS_POS_[n]
using the Status-Flags (OVERRIDDEN) and now also in the property Reliability.
Changes of the Status-Flags generate COV-Notifications (if enabled)
Handling of network priorities corrected
Increased MS/TP communication quality on MS/TP
Known issues:
–
Firmware V1.09
New functions/modifications:
The disengaged gear is represented on the objects ACT_VALUE_[n] and ABS_POS_[n]
using the Status-Flags (OVERRIDDEN)
Known issues:
–
Firmware V1.08
New functions/modifications:
OFFSET_DEV_ID Setting adjusted to
0…4'194'056 (2
22
-247)
New functional profile "MPL actuator" supported (e.g. CQ24A-MPL)
Integrated sensor conversion
°C for PT1000, NI1000 and NTC5K
Nominal volumetric flow (VAV/EPIV) as BACnet Object available
MP addressing function reworked
Known issues:
–
Firmware V1.07
New functions/modifications:
WritePropertyMultiple service supported
Feedback values are rounded
Unconfirmed-COV-Notification for Multi-state Value fixed (wrong datatype)
PropertyIdentifier for COV_Increment fixed (wrong ID)
Sending of malformed packets fixed (in relation with WhoIs requests)
Instability on high baudrate (76.8k) resolved
Known issues:
–
Firmware V1.06
New functions/modifications:
Unsolicited-COV-Reporting for volumetric flow added
Engineering units (position/volumetric flow/pressure) is updated (if supported by actuator)
Instability on high bus load resolved
Known issues:
WritePropertyMultiple service not supported
Firmware V1.03
New functions/modifications:
Property State_Text changed to BACnetARRAY
Property Description in SUM_FAULT object with bit field (internal state) completed
Unsolicited-COV-Reporting supported (see known issues)
Absolute position ABS_POS_[n] calculated
Known issues:
WritePropertyMultiple service not supported
Engineering units (position and volumetric flow) not for all actuator types updated
Unsolicited-COV-Reporting for volumetric flow not supported