Belimo GMB24-SR Скачать руководство пользователя страница 1

800-543-9038 

USA

866-805-7089 

CANADA

203-791-8396 

LATIN AMERICA

187

GM Series Direct Coupled Actuator

A

Actuators in
bold have BDCM

GM Series - At A Glance

Basic Product

Flexible Product

Torque

360 in-lb [40 Nm]

Angle of Rotation

95 degrees

Power Supply

24 VAC/DC

100 to 240 VAC

Control Input

On/Off, Floating Point

2 to 10 VDC (4 to 20mA)

Multi-Function Technology

0 to 135 Ohm

0 to 20V Phasecut

LonWORKS

®

Feedback

None

2 to 10 VDC

Variable (0 to 10 VDC)

Running Time

150 seconds

Adj. 75 to 280 seconds

Wiring

Plenum Rated Cable

Appliance Rated Cable

Conduit Fitting

Auxiliary Switch

Add-On

Installation and Operations…(page 269).

*Based on 4 in-lb/ft

2

damper torque loading.  Parallel blade.  No edge seals.  

GMX24-MFT95 

(p.

 203)

GMB(X)24-3 

(p.

 189)

GMX120-3 

(p.

 193)

GMB(X)24-SR 

(p.

 195)

GMB(X)24-MFT 

(p.

 199)

GMX24-PC 

(p.

 205)

GMX24-LON 

(p.

 207)

Minimum 360 in-lb Torque

For damper areas up to 90 sq-ft*

GMB24-3-T N4 

(p.

 191)

GMB24-SR-T N4 

(p.

 197)

GMX24-MFT

-T N4 

(p.

 201)

 M40024 - 05/10 - Subject to change.

 © Belimo 

Aircontrols (USA),

 Inc.

Содержание GMB24-SR

Страница 1: ...iable 0 to 10 VDC Running Time 150 seconds Adj 75 to 280 seconds Wiring Plenum Rated Cable Appliance Rated Cable Conduit Fitting Auxiliary Switch Add On Installation and Operations page 269 Based on 4...

Страница 2: ...Potentiometer Add Ons Mount Directly on Clamp Includes Conduit Connector Standard 3ft Plenum Rated Cable and Conduit Connector Provided on Basic Models Added Flexibility to Select Clamp Electrical Con...

Страница 3: ...int control of dampers in HVAC systems Actuator sizing should be done in accordance with the damper manufacturer s specifications The actuator is mounted directly to a damper shaft up to 1 05 in diame...

Страница 4: ...ng Bracket Z GMA GM to GM Retrofit Mounting Bracket ZG GMA Crank arm Adaptor Kit ZG JSA 1 2 3 Jackshaft Adaptors for Hollow Jackshafts ZS 100 Weather Shield Steel ZS 150 Weather Shield Polycarbonate Z...

Страница 5: ...ntrol of damper surfaces up to 90 sq ft Application For on off and floating point control of dampers in HVAC systems Actuator sizing should be done in accordance with the damper manufacturer s specifi...

Страница 6: ...erride on the cover of the actuator Run time shall be constant and independent of torque Actuators shall be cULus listed have a 5 year warranty and be manufactured under ISO 9001 International Quality...

Страница 7: ...off and floating point control of dampers in HVAC systems Actuator sizing should be done in accordance with the damper manufacturer s specifications The actuator is mounted directly to a damper shaft...

Страница 8: ...Shaft Clamp ZG 102 Multiple Actuator Mounting Bracket Z GMA GM to GM Retrofit Mounting Bracket ZG GMA Crank arm Adaptor Kit ZG JSA 1 2 3 Jackshaft Adaptors for Hollow Jackshafts ZS 100 Weather Shield...

Страница 9: ...ystems Actuator sizing should be done in accordance with the damper manufacturer s specifications The actuator is mounted directly to a damper shaft up to 1 05 in diameter by means of its universal cl...

Страница 10: ...tronic controller or positioner Actuators shall have Brushless DC motor technology and be protected from overload at all angles of rotation Actuators shall have reversing switch and manual override on...

Страница 11: ...ems Actuator sizing should be done in accordance with the damper manufacturer s specifications The actuator is mounted directly to a damper shaft up to 1 05 in diameter by means of its universal clamp...

Страница 12: ...rload at all angles of rotation Actuators shall have reversing switch and manual override on the cover of the actuator Run time shall be constant and independent of torque A 2 to 10 VDC feedback signa...

Страница 13: ...zing should be done in accordance with the damper manufacturer s specifications The actuator is mounted directly to a damper shaft up to 1 05 in diameter by means of its universal clamp A crank arm an...

Страница 14: ...sted have a 5 year warranty and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide overload protection and di...

Страница 15: ...For proportional modulation of dampers in HVAC systems Actuator sizing should be done in accordance with the damper manufacturer s specifications The actuator is mounted directly to a damper shaft up...

Страница 16: ...uators shall be cULus listed have a 5 year warranty and be manufactured under ISO 9001 International Quality Control Standards Actuators shall be as manufactured by Belimo Wiring Diagrams 1 Provide ov...

Страница 17: ...turer s specifications The actuator is mounted directly to a damper shaft up to 1 05 in diameter by means of its universal clamp A crank arm and several mounting brackets are available for application...

Страница 18: ...d Actuators with appliance cables are numbered 21 Provide overload protection and disconnect as required 22 2 Actuators and controller must have separate transformers 23 3 Consult controller instructi...

Страница 19: ...The actuator is mounted directly to a damper shaft up to 1 05 in diameter by means of its universal clamp A crank arm and several mounting brackets are available for applications where the actuator ca...

Страница 20: ...g switch and manual override on the cover Run time shall be constant and independent of torque Actuators shall be cULus listed have a 5 year warranty and be manufactured under ISO 9001 International Q...

Страница 21: ...nal T i i lb f l f d f f Torque min 360 in lb for control of damper surfaces up to 90 sq ft Application Direct coupled actuators for direct link to LonWorks network Actuators are easily installed by d...

Страница 22: ...reversing switch and manual override on the cover Run time shall be constant and independent of torque A Actuators shall be cULus listed have a 5 year warranty and be manufactured under ISO 9001 Inter...

Страница 23: ...output variable shows the current angle of rotation of the actuator or the valve and can be used to display the position or for service purposes nvoAbsAirFlow SNVT_flow This output variable is inacti...

Страница 24: ...ected and ready for operation in the LONWORKS network Yellow on No application software is loaded in the SR24ALON 5 Yellow flashing flashing interval 2 seconds The SR24ALON 5 is ready for operation bu...