background image

   

 

 

 

 

 

 

 

 

 

    

  

 
 

Cross Reference 

 
For greater detail see 

www.belimo.us/firesmoke

 RETROFIT or  download from 

https://www.belimo.us/mam/americas/technical_documents/pdf-
web/fire_and_smoke_doc/fire_smoke_competitive_replacement_data_reference.pdf

 

 

Honeywell 

Voltage 

Control 

Torque 

Aux 

Replacement 

  

ML4105A1000 

120 VAC 

On/Off 

30 

  

FSLF120 US 

ML4105B1009 

120 VAC 

On/Off 

30 

  

FSLF120 US 

ML4105C1008 

230 VAC 

On/Off 

30 

  

FSLF230 US 

ML4105D1007 

230 VAC 

On/Off 

30 

  

FSLF230 US 

ML4115A1009 

120 VAC 

On/Off 

30 

  

FSLF120 US 

ML4115A1017 

120 VAC 

On/Off 

30 

  

FSLF120 US 

ML4115B1008 

120 VAC 

On/Off 

30 

  

FSLF120 US 

ML4115B1016 

120 VAC 

On/Off 

30 

  

FSLF120 US 

ML4115C1007 

230 VAC 

On/Off 

30 

  

FSLF230 US 

ML4115C1015 

230 VAC 

On/Off 

30 

  

FSLF230 US 

ML4115D1006 

230 VAC 

On/Off 

30 

  

FSLF230 US 

ML4115D1014 

230 VAC 

On/Off 

30 

  

FSLF230 US 

ML4115H1002 

120 VAC 

On/Off 

30 

  

FSLF120 US 

ML4115J1019 

120 VAC 

On/Off 

30 

  

FSLF120 US 

ML4202F1000 

120 VAC 

On/Off 

20 

  

FSLF120 US 

ML4202F1000 

120VAC 

On/Off 

20 

  

FSLF120 US 

ML4302F1008 

120 VAC 

On/Off 

20 

  

FSLF120 US 

ML8105A1006 

24 VAC 

On/Off 

30 

  

FSLF24 US 

ML8105B1005 

24 VAC 

On/Off 

30 

  

FSLF24 US 

ML8115A1005 

24 VAC 

On/Off 

30 

  

FSLF24 US 

ML8115A1013 

24 VAC 

On/Off 

30 

  

FSLF24 US 

ML8115B1004 

24 VAC 

On/Off 

30 

  

FSLF24 US 

ML8115B1012 

24 VAC 

On/Off 

30 

  

FSLF24 US 

ML8115H 

24 VAC 

On/Off 

30 

  

FSLF24 US 

ML8115J 

24 VAC 

On/Off 

30 

  

FSLF24 US 

ML8202 

24 VAC 

On/Off 

20 

  

FSLF24 US 

ML8302 

24 VAC 

On/Off 

20 

  

FSLF24 US 

MS4104F1010 

120 VAC 

On/Off 

30 

  

FSLF120 US 

MS4104F1210 

120 VAC 

On/Off 

30 

FSLF120-S US 

MS4109F1010 

120 VAC 

On/Off 

80 

  

FSNF120 US 

  

MS4109F1210 

120 VAC 

On/Off 

80 

FSNF120-S 

  

MS4120F1006 

120 VAC 

On/Off 

175 

  

FSAFA120 

  

MS4120F1204 

120 VAC 

On/Off 

175 

FSAF120A-S 

  

MS4209F1007 

120 VAC 

On/Off 

80 

  

FSNF120 US 

  

Safe-Air Honeywell ML & MS Motors with Belimo FSNF120 Series              March 2018  

 

 

 

Содержание FSNF120 US

Страница 1: ...6 Wiring 17 Building Official Fire Marshal Notification Form 19 Contacts Chris Sheehan 203 749 3112 Larry Felker 775 355 2461 775 250 4160 Cell Mike Knipple 203 749 3170 Laure Pomianowski 775 355 2466 800 543 9038 www belimo us firesmoke WARNING Installer must be trained and experienced with repair of fire and smoke dampers and actuators WARNING Before replacing actuator damper must be inspected a...

Страница 2: ... Fire Marshal and or Building Official must be consulted if any blade or auxiliary switches are employed and are connected to the fire alarm system or to a Fire Fighters Smoke Control System FSCS panel Retesting is required A permit and inspection may be required since connections to an alarm system have been touched In the Marking Application Guide Dampers for Fire Barrier and Smoke Applications ...

Страница 3: ...n d If the damper is equipped with a fusible link the link shall be removed for testing to ensure full closure and lock in place if so equipped If the link is damaged or painted it shall be replaced with a link of the same size temperature and load rating e The fusible link shall be reinstalled after testing is complete After installation and wiring of new actuator it shall be tested a The checkli...

Страница 4: ...ve the same voltage rating as the original Amperage the replacement actuator s shall not draw more amperage than the original s and cause the total connected amp draw on a circuit breaker to be greater than allowed by electrical code Final Testing actuated damper and associated devices shall be tested for proper operation See Acceptance testing details below Mnemonic device TTT VAT For the Air Mov...

Страница 5: ... FSLF230 US ML4115H1002 120 VAC On Off 30 FSLF120 US ML4115J1019 120 VAC On Off 30 FSLF120 US ML4202F1000 120 VAC On Off 20 FSLF120 US ML4202F1000 120VAC On Off 20 FSLF120 US ML4302F1008 120 VAC On Off 20 FSLF120 US ML8105A1006 24 VAC On Off 30 FSLF24 US ML8105B1005 24 VAC On Off 30 FSLF24 US ML8115A1005 24 VAC On Off 30 FSLF24 US ML8115A1013 24 VAC On Off 30 FSLF24 US ML8115B1004 24 VAC On Off 30...

Страница 6: ...30 VAC On Off 175 FSAF230A S20230 F SW2 230 VAC On Off 175 2 FSAF230A S S2024 F 24 VAC On Off 175 FSAF24A S2024 F SW2 24 VAC On Off 175 2 FSAF24A S SPH2 Aux Switch 32003532 002 Aux Switch Use FSNF series if damper is 4 sq ft Use S model of proper voltage Nominal sq ft per UL555S testing Temp Actuator 4 350 F FSLF 36 w x 24 h also 12 350 F FSNF Multisections also 16 250 F FSNF Multisections also 18...

Страница 7: ...e Link 24 Vac ASK79 165 165 F 74 C BAE165 US ASK79 212 212 F 100 F None Call if needed ASK79 250 250 F 121 C None Call if needed ASK79 350 350 F 177 C None Call if needed Optional Two Auxiliary Switches Fixed 5 and 85 FSTF Best solution for small dampers where the HW bracket has been hung out into the air is to use an FSTF actuator Safe Air Honeywell ML MS Motors with Belimo FSNF120 Series March 2...

Страница 8: ...20 5800EMB1 FSLF120 5800EMB1 Outside the duct top mount power open 5800EMB7 FSLF120 5800EMB7 Inside the duct bottom mount power closed 5800EMB10 FSLF120 5800EMB10 Outside the duct bottom mount power closed 5800EMB5 FSLF120 5800EMB5 Inside the duct top mount power open 5800EMB8 FSLF24 5800EMB9 FSLF120 While direct coupling is preferable some applications require linkages See Linkages below for an e...

Страница 9: ...ons Typically these were linkaged using a crank arm on the square shaft and the spring was on the round shaft Remove all linkage parts and direct couple to damper shaft 10 See Greenheck Installation Instructions Typically these were linkaged using a crank arm on the square shaft and the spring was on the round shaft Remove all linkage parts and direct couple to damper shaft 11 Some were direct cou...

Страница 10: ...tation Anti External view Belimo FSNF mounts on shaft with the clamp on the side of the actuator necessary to spring closed Internal view The fusible link releases a spring that closes the damper This should not be modified Where a J box is needed for wiring a chase nipple and 2x4 or 4x4 box can be attached to the actuator Safe Air Honeywell ML MS Motors with Belimo FSNF120 Series March 2018 10 ...

Страница 11: ...ch so that this is prevented A 4 x 4 or larger electrical plate will serve as an anti rotation mounting plate if old actuator is hung over free air See Belimo Mounting Methods Guide Anti rotation strap can be attached to bracket 4 x 4 plate or sheet metal bracket WARNING USE CAUTION Spring is under high torsion and may cause serious injury If any external springs are present exercise caution wear ...

Страница 12: ...with actuator Bolts and lock nuts Anti rotation strap 11695 LF P The heavier duty 11414 AF P may be ordered when needed Bend strap at perforations to adjust for necessary height WARNING Read Data Sheet provided in box with each actuator for specific wiring details WARNING Actuator anti rotation strap may not be screwed to the duct It must attach to either the sleeve or to the mounting bracket The ...

Страница 13: ... should be parallel to the plane of the damper frame and sleeve Actuator must be perpendicular to the damper shaft Allow any non concentric shaft motion to be taken up by mounting stud in middle of U slot Figure 1 Figure 2 Figure 3 As long as it is mechanically solid the anti rotation strap may be bent to fit height Note how the pin of the anti rotation strap is mounted in middle of actuator U slo...

Страница 14: ...tor for specific wiring details Belimo linkage kits https www belimo com pim mam americas technical_documents d ata_sheets man air acc Mechanical_Accessories pdf Mounting Methods Guide https www belimo us mam americ as technical_documents pdf web guides mounting_methods pdf Safe Air Honeywell ML MS Motors with Belimo FSNF120 Series March 2018 14 ...

Страница 15: ...is in front of blade ZG DC2 Damper blade clip and ball joints typically used for 6 wide blade control dampers Typically the ctuator or rod to shaft is above or below the damper KH 6 Zinc plated steel For shafts 3 8 to 11 16 Uses KG6 ball joint Slot width 1 4 KH 8 Zinc plated steel For shafts 3 8 to 11 16 Uses KG8 90 degree or KG10A ball joint Slot width 21 64 Where the crank arm on the jackshaft i...

Страница 16: ...ay be used Belimo S2A F S models H C 165 F Contact closed if damper closed Contact closes if damper open S2 S1 Internal switches C H Hot Closed Open Manual reset Some models are SPDT Check data sheets Switch cable Belimo BAE165 US Where existing sensor is defective or one must be added the 165 F primary sensor may be used Belimo S2A F FSLF mid 2014ff FSNF FSAF actuators can use the add on switch p...

Страница 17: ...s a basis for any of the other wiring schematics Note that the alarm connections are not touched when replacing an actuator This is a major concern for Fire Marshals In some rare cases fusible links may have been used In those cases the wiring for the actuator will be similar to this HOT 120 or 24 VAC Smoke Detector or Relay from area smoke detection system BELIMO FSxx ACTUATOR N or COM Fusible li...

Страница 18: ... FSCS The auxiliary switches are used to provide status indication to the fire fighters smoke control panel Typically there are two or three status lights or leds This wiring is the responsibility of the fire alarm company If it is touched they must retest to verify proper operation These switches are not alarm but rather indicating WARNING Damper must be free to move from open to closed without u...

Страница 19: ...ke detector or relay contacts Actuator springs damper closed b Reconnect power Actuator drives damper open c Trip thermal sensor Actuator springs damper fully closed d Press manual reset Actuator drives damper open Test FSCS switch functions a Move FSCS switch to Off position Actuator springs damper fully closed b Move FSCS switch to Hand position Actuator drives damper open c Trip secondary highe...

Отзывы: