Installation RS20/RS30-...U
Release 03 08/2019
29
2.2.1
Installing the device onto the DIN rail
Verify that the device maintains the minimum clearing in order to meet the
climatic conditions:
Top and bottom device side: 3.94 in (10 cm)
Left and right device side: 0.79 in (2 cm)
To mount the device onto a horizontally mounted 35 mm DIN rail according
to DIN EN 60715, proceed as follows:
Slide the upper snap-in guide of the device into the DIN rail.
Pull down the locking gate using a screwdriver and press the lower part
of the device against the DIN rail.
Snap in the device by releasing the locking gate.
Note:
The overall shield of a connected shielded twisted pair cable is
connected to the ground connector on the front panel as a conductor.
2.3
Grounding the device
For the ground conductor, use a wire diameter of at least 1.0 mm².
The device is grounded by the separate ground screw on the front panel.
2.4
Installing an SFP transceiver (optional)
Use only Hirschmann SFP transceivers which are suitable for usage with the
device.