CONTROL DRAWING for Industrial ETHERNET
Rail Switch 2 and Rail Transceiver 2 Family

According to ANSI / ISA 12.12.01-2012

Rev.: 0 Date: 2012-07-13

Document No.:  000163806DNR

Page 1 of 1

NON HAZARDOUS LOCATION

Power Supply: (Redundant: P1, P2)
 24 

DC

Relay Contacts:

Associated Apparatus:

Equipment with nonincendive 
fi eld wiring 

1

HAZARDOUS LOCATION Class 
I, Division 2 Groups A, B, C, D

The Use in Hazardous Locations is only allowed for Rail Switch 2 and Rail Transceiver 2 Family model No‘s which are individually labelled 

FOR USE IN CLASS I, DIVISION 2 HAZARDOUS LOCATIONS

Notes:

 

The nonincendive fi eld wiring circuit concept allows interconnection of nonincendive fi eld wiring apparatus and associated nonincendive 

fi eld wiring apparatus using any of the wiring methods permitted for unclassifi ed locations when certain parametric conditions are met

Capacity:  

Ca ≥ Ci + CCable 

Inductivity:   

La ≥ Li + LCable 

The maximum cable length has to be determined as follows:
(a) max. Cable Length < (La - Li) / 

LCable 

and (b) max. Cable Length < (Ca - Ci) / 

CCable

 

The lower value of (a) and (b) is to apply.
CableL: inductance per unit length of used cable.

CableC: capacitance per unit length of used cable.

Other C-parameters and L-parameters are according to ANSI / ISA 12.12.01-2012 section 7.

Where cable capacitance and inductance values per foot are not known, the following values shall be used:

CCable

 60 pF/foot, 

LCable

 0.2 µH/foot

Nonincendive fi eld wiring circuits must be wired in accordance with the National Electric Code (NEC), NFPA 70, article 501.

1

Nonincendive Field Wiring Parameters:

The Relay Contacts are dependent upon the 

following Entity Parameters:

V

max

I

max

C

i

L

i

30 V

90 mA

2.5 nF

1 µH

WARNING – EXPLOSION HAZARD – SUBSTITUTION OF ANY COMPONENTS MAY IMPAIR SUITABILITY FOR HAZAR-

DOUS LOCATIONS OR EXPLOSIVE ATMOSPHERES.

WARNING – EXPLOSION HAZARD – DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR 
THE AREA IS KNOWN TO BE NON-HAZARDOUS.

DO NOT OPEN WHEN ENERGIZED.

Relay Contacts:

Associated Apparatus:

Equipment with nonincendive 
fi eld wiring 

1

Power Supply: (Redundant: P1, P2)
 24 

DC

Detail: RS2-xxx

Detail: RT2-xxx

The equipment must be installed in a tool-locked enclosure.

Содержание Hirschmann RS2-TX

Страница 1: ...standard 802 3 using copper technolo gy The switch modules are plugged onto the standard bar The RS2 TX modules have eight 10 100 MBit s twisted pair ports RJ45 connectors It is possible to connect up...

Страница 2: ...components recommen ded or approved by Hirschmann The product can only be operated correctly and safely if it is transpor ted stored installed and assembled properly and correctly Furthermore it must...

Страница 3: ...Li LCable and b max Cable Length Ca Ci CCable The lower value of a and b is to apply CableL inductance per unit length of used cable CableC capacitance per unit length of used cable Other C parameters...

Страница 4: ...structions This device is electrically operated Adhere strictly to the safety requirements relating to voltages applied to the device as described in the operating instructions z Warning Failure to ob...

Страница 5: ...voltage 2 less than 9 6 V FAULT Failure red LED lit The indicator contact is open i e it indicates an error not lit The indicator contact is closed i e it does not indicate an error Port Status These...

Страница 6: ...onnect up to eight data ter minal equipments DTE or other network segments to the 10 100 Mbit s ports of the RS2 TX using twisted pair cabling ref Fig 4 3 Assembly startup procedure and dismantling 3...

Страница 7: ...61000 4 5 Test level 3 Cable based RF faults EN 61000 4 6 Test level 3 EMC emitted immunity EN 55022 Class A CFR 47 Part 15 Class A Germanischer Lloyd Rules for Classification and Construction VI 7 3...

Страница 8: ...Automation and Control GmbH Stuttgarter Stra e 45 51 72654 Neckartenzlingen Germany Tel 49 0 1805 14 1538 Fax 49 0 7127 14 1551 E mail hac support belden com Internet http www hirschmann com 039 663 0...

Отзывы: