OpEdge
Industrial Edge Gateway – Release 01.0.00 – 10/2022
7.2 Factory Reset – Command Line Interface
To reset the OpEdge to factory default using the CLI, perform the following steps:
1
Connect to the console port of the OpEdge-8D using a Terminal Emulator like Tera Term
or Putty.
2
Select the COM Port on which the console shall be connected.
3
Set the below mentioned parameters for the Serial Ports:
a)
Baud Rate/ Speed: 115200
b)
Data: 8 bit
c)
Parity: None
d)
Stop Bits: 1 bit
e)
Flow Control: None