National and international safety regulations
Verify that the electrical installation meets local or nationally applicable
safety regulations.
Grounding the device
Grounding the device is by means of a separate ground connection on the
device.
Ground the device before connecting any other cables.
Disconnect the grounding only after disconnecting all other cables.
Shielding ground
The overall shield of a connected shielded twisted pair cable is connected
to the ground connector on the front panel as a conductor.
Beware of possible short circuits when connecting a cable section with
conductive shielding braiding.
Requirements for connecting electrical wires
Before connecting the electrical wires,
always
verify that the
requirements listed are complied with.
All
of the following requirements are complied with:
The electrical wires are voltage-free.
The cables used are permitted for the temperature range of the application case.
Only for device variants featuring supply voltage with the characteristic value CC:
The voltage connected complies with the requirements for a safety extra-low voltage
(SELV) as per IEC/EN 60950-1.
Table 1:
General requirements for connecting electrical wires
All
of the following requirements are complied with:
The voltage connected complies with the requirements for a safety extra-low voltage
(SELV) as per IEC/EN 60950-1.
The connected voltage is limited by a current limitation device or a fuse.
Observe the electrical threshold values for the signal contact.
See “General technical data” on page 44.
The cross-section of the ground conductor is the same size as or bigger than the cross-
section of the power supply cables.
Table 2:
Requirements for connecting the signal contact