Technical data
102
11.8 LEDs
Technical manual LioN-P PROFINET IO-Link Master
Release 2.0 04/2017
11.8
LEDs
U
Aux
Green
Auxiliary sensor/actuator voltage approx.
>18,6 V - <30 V
red*
Auxiliary sensor/actuator voltage approx.
<18 ,6 V or >30 V
* if "Report U(Aux) supply voltage fault" is
enabled.
off
None of the above conditions
U
S
Green
System/sensor voltage approx. >18,6 V - 30 V
off
System/sensor voltage approx. <18,6 V - 30 V
X1…X8 A
Green
IO-Link COM mode: IO-Link communication
exists
Flashing green
IO-Link COM mode: No IO-Link communication.
Yellow
Standard-I/O mode: Status of digital input or
output on C/Q (pin 4) line "on"
off
None of the above conditions
X1…X8 B
White
Status of digital input on pin 2 line "on"
red
IO-Link COM mode: IO-Link communication error
or
Overload or short circuit on C/Q (pin 4) line
red
All modes: Overload or short circuit on L+ (pin 1)
line
red
SIO mode: Overload or short circuit on C/Q
(pin 4) line
off
None of the above conditions
P1 Lnk/Act
P2 Lnk/Act
Green
Ethernet connection to another subscriber exists.
Link detected.
Flashing yellow
Data exchange with another subscriber.
off
No connection to another subscriber. No link, no
data exchange.
BF
Red
Bus fault. No configuration, no or slow physical
connection
Red flashing at 2 Hz
Link exists but no communication link to the
PROFINET controller
off
PROFINET controller has established an active
connection to the device
DIA
Red
PROFINET diagnostic alarm active
Red flashing at 1 Hz
Watchdog time-out; fail safe mode is active
Red flashing at 2 Hz, 3 sec
DCP signal service is initiated via the bus
Red double flash
Firmware update
off
None of the above conditions
Table 51: Information on the LED colors
Содержание 934 840 001
Страница 2: ...2 Technical manual LioN P PROFINET IO Link Master Release 2 0 04 2017...
Страница 6: ...Content 6 Technical manual LioN P PROFINET IO Link Master Release 2 0 04 2017...
Страница 14: ...Designations and synonyms 14 Technical manual LioN P PROFINET IO Link Master Release 2 0 04 2017...
Страница 34: ...Assembly and wiring 34 5 3 Port assignments Technical manual LioN P PROFINET IO Link Master Release 2 0 04 2017...