Diagnostics processing
Technical manual LioN-Link BusHead EtherNet/IP™
Release 1.1 04/2016
8.4 Behavior in case of a diagnostic
overflow
53
8.4
Behavior in case of a diagnostic overflow
If all the diagnostic blocks are populated with diagnoses, an overflow
message is sent in the last free diagnostic block.
In this case, new diagnoses can only be displayed in detail again if all active
diagnoses have become inactive or were acknowledged (Acknowledge
Mode) in the meantime.
The overflow diagnosis remains active until there are no longer any active
diagnoses in the system. Any remaining modules with diagnostics, whose
diagnostic information could not be reported via a diagnostic block, can be
viewed via the web server. Alternatively, these data can also be read
acyclically from the BusHead using Class ID 0x64 / instance 1 / attribute 1,
see chapter
18
0x12
I/O module failure
19
0x13
Diagnostics I/O module
20
0x14
Configuration fault (Use Web-Interface for detailed information)
21
0x15
Common I/O fault
22
0x16
Over current motor
23
0x17
Common motor fault
24
0x18
Internal module fault
25
0x19
Fuse defective
26
0x1A
Limit value exceeded
27
0x1B
Calibration fault
28
0x1C
Incorrect module
29
0x1D
Module missing
30
0x1E
Reserved
31
0x1F
Reserved
100
0x64
RPI warning
101
0x65
IP address conflict
254
0xFE
Internal information: Send only channel diagnostics and no
additional accumulative diagnostics
255
0xFF
Diagnosis overflow
Diagnostic
Code
Description
Table 14: Diagnostic messages
Содержание 934 815-001
Страница 2: ...2 Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...
Страница 6: ...Contents 6 Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...
Страница 10: ...About this manual 6 1 3 Version information Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...
Страница 18: ...System description 14 3 2 Product overview Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...
Страница 28: ...Assembly and wiring 24 4 4 Port assignments Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...
Страница 32: ...Starting operation 28 5 3 IP address Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...
Страница 68: ...Technical data 64 9 4 LEDs Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...
Страница 70: ...Declaration of conformity 66 Technical manual LioN Link BusHead EtherNet IP Release 1 1 04 2016...