INSTALLATION INSTRUCTION 

 

 

Manufacturer 

Bel Fuse Inc. 

206 Van Vorst St. 

Jersey City  

NJ 07302, USA 

Asia-Pacific 

+86 755 2988 5888

 

Europe, Middle East 

+353 61 225 977

 

North America 

+1

 

408

 

785 5200

 

© 2021 Bel Power Solutions & Protection

 

BCM.00430_AE

 

 

USER INSTRUCTIONS

 

1) DESCRIPTION 

DIN rail mountable primary switched-mode power supply with 90 - 264 VAC (110 - 345 VDC) input, suitable for single phase mains line and DC line. 

2) INSTALLATION 

Use DIN-rails according to EN60715. Installation should be made vertically (see Fig.4). For better device stability fix the rail to the wall close to the point where the device 
is to be mounted. In order to guarantee sufficient convection, we recommend observing a minimum distance to other modules (see Fig.3).  

The device is provided with a thermal protection; a limited air flow can cause the thermal protection tripping. 

The SMPS automatically restarts after cooling. To get normal operation reduce the temperature of the air surrounding the power supply, increase the ventilation or reduce 
the load (see Fig.8) 

3) CONNECTIONS

 

The device is equipped with screw terminal blocks. To avoid sparks, do not connect or disconnect the connectors before having previously turned-off input power and 
waited for internal capacitors discharge (minimum 1 minute) 

In order to comply with UL certification, use appropriate copper cables of indicated cross section, designed for an operating temperatures of: 

60°C for ambient up to 45°C 

75°C for ambient up to 60°C 

90°C for ambient up to 70°C 

Strip the connecting ends of the wires according to the indication and ensure that all strands of a stranded wire enter the terminal connection (see Fig.5) 

4) INPUT PROTECTION

 

The device input is provided with varistors against overvoltage. Input is provided with internal fuse 2AT / 250 VAC thus an external short circuit/overcurrent protection 
must be provided by the end user (see Fig.6). 

For operation on a single-phase system, a protection fuse on the phase must be provided. 

Surge protection:

 it is strongly recommended to provide external surge arresters (SPD) according to local regulations. 

5) AC INPUT CONNECTION

 

The device can be connected to single phase AC line with rated Vin 120 - 240 VAC (see Fig.7). 

6) DC INPUT CONNECTION 

Connect L terminal to (+) positive pole, N terminal to (-) negative pole. Rated voltage 110 

 345 VDC. 

The device is also suitable for photovoltaic or wind turbine applications (see Fig.7). 

7) OUTPUT CONNECTION 

The device is suitable for 

SELV

 and 

PELV 

circuitry. 

Vout can be adjusted with a potentiometer to a wide range (see Fig.1), only on Models LDN40-5, LDN40-12 and LDN40-12D. 

Check Vout before connecting the power supply to the load. With output voltage set to the max. value, the continuous [current x voltage] must not exceed the nominal 
power. 

8) PARALLEL CONNECTION AND REDUNDANCY

 

Power supplies can be connected in parallel to increase power. 

Vout must be set uniformly (±100 mV) on each power supply and the wiring must be symmetrical to ensure an equal current distribution. 

For redundant connection, use an external isolating device must be used (see accessory device). 

9) OUTPUT PROTECTION 

The device is protected against overload (OL) / short circuit (SC) / overvoltage (OV) / overtemperature (OT).

 

OL and SC:

 are controlled by a hiccup mode auto-reset protection with the following behaviour.

 

OL behaviour:

 Max. OL = In x 1.5 with constant output voltage. If the current is 

 In x 1.5 the unit enters the OL protection and starts an ON/OFF cycle (hiccup mode). 

SC behaviour:

 the device supplies the indicated short circuit peak current for 30 ms if the output current exceeds In x 1.5 the device enters into a controlled ON/OFF 

cycles (hiccup mode). The output voltage drops to a voltage value depending on the impedance of the failed load circuit. 

Output OV circuit protection

: the output is protected against potential OV due to internal malfunction or coming from the load for  

Vout 

 Vnom x 1.2 

 1.3, depending on the model. 

 

OT protection:

 turns off the device if the internal temperature exceeds a safe limit. 

The device restarts automatically after cooling down. To recover to normal operation reduce air temperature surrounding the power supply, increase cooling or reduce 
load (see Fig.8). 

10) FEEDING DC MOTORS 

It is possible to feed DC motors considering that when a motor starts-up under effort its consumption is much higher than the nominal current and it can trigger 
overcurrent protection (see accessory device). 

NOTE:

 motors can generate high conducted noise on the DC line. Therefore, it is not recommended to feed on the same line motors and equipment sensitive to noise. 

 

 

 

Содержание LDN40-5

Страница 1: ...efore touching it Do not allow liquids or foreign objects to enter into the products To avoid sparks do not connect or disconnect the device before having previously turned off input power and wait for internal capacitors discharge minimum 1 minute GEFAHR VON VERBRENNUNGEN EXPLOSIONEN FEUER STROMSCHLAG PERSONENSCHÄDEN Führen Sie niemals Arbeiten an spannungsführenden Teilen durch Gefahr von tödlic...

Страница 2: ...20 240 VAC see Fig 7 6 DC INPUT CONNECTION Connect L terminal to positive pole N terminal to negative pole Rated voltage 110 345 VDC The device is also suitable for photovoltaic or wind turbine applications see Fig 7 7 OUTPUT CONNECTION The device is suitable for SELV and PELV circuitry Vout can be adjusted with a potentiometer to a wide range see Fig 1 only on Models LDN40 5 LDN40 12 and LDN40 12...

Страница 3: ... 90 3 54 Distance A B mm inc 10 0 4 10 0 4 FIG 4 MOUNTING DISMOUNTING INSTRUCTIONS For DIN rail fastening according to IEC 60715 TH35 7 5 15 Mounting as shown in figure with input terminals on lower side with suitable cooling and maintaining a proper distance between adjacent devices as specified in the Installation Instruction of each family MOUNTING 1 Tilt the unit slightly backwards 2 Fit the u...

Страница 4: ...he European equivalent type Surge protection it is strongly recommended to provide external surge arresters SPD according to local regulations FIG 7 INPUT CONNECTIONS AC LINE DC LINE FIG 8 ENVIRONMENT OPERATING TEMPERATURE DERATING 40 C to 70 C 5 95 r H non condensing UL Certified up to 50 C LDN40 5 LDN40 12D LDN40 12 LDN40 24 0 25 W C over 50 C 0 25 W C over 50 C 0 35 W C over 50 C 0 35 W C over ...

Отзывы: