7. ELECTRICAL SYSTEM DESIGN FOR INSTALLATION IN
    HAZARDOUS AREAS USING GALVANIC ISOLATORS.

Galvanic isolators although more expensive than Zener barriers, do not
require a high integrity earth connection. For small systems where a high
integrity earth is not already available, the use of galvanic isolators often
reduces the overall installation cost and simplifies design.

7.1  Single stage alarm

BR385 sounders may be powered by any Ex ia ATEX certified galvanic
isolator having output parameters within the limits specified in section 4.3.
The sounder may be controlled by turning the galvanic isolator on and off,
or from the hazardous area by a mechanically activated switch complying
with the requirements for simple apparatus as defined by EN 60079-11.
i.e. having IP20 protection and able to withstand a 500V rms insulation
test to earth for one minute.    

Fig 7  Single stage alarm using galvanic isolator

.

7.2  Multi-stage alarm

Fig 8 shows a typical application in which the first and second stage alarm
tones are activated by the alarm outputs of a BA327E intrinsically safe
loop powered indicator. The BA327E alarm outputs have been certified as
simple apparatus and may therefore be used to switch the BR385 sounder
in the hazardous area.   The contacts of most certified intrinsically safe
relays may also be used in the same way.

Fig 8  Loop-powered BA327E intrinsically safe indicator

       activating BR385 first and second stage alarms

8. ACCESSORIES
8.1 Tag number

BR385 sounders can be supplied identified by a tag  number thermally
printed on a self adhesive label. 

9. SERVICING

No attempt should be made to repair a faulty BR385 sounder.    Suspect
sounders should be returned to BEKA associates or our local agent for
repair.

10. GUARANTEE

Sounders  which fail within  the guarantee  period  should  be returned  to
BEKA associates or our local agent.  It is helpful if a brief description of
the fault symptoms is provided.

11. CUSTOMER COMMENTS

BEKA associates is always pleased to receive comments from customers
about our products and services.  All communications are acknowledged
and whenever possible, suggestions are implemented.

4

Содержание BR385

Страница 1: ...alvanic isolator that will supply between 8 and 28V at the and terminals of the sounder Sounders may be tested or used in safe areas without a Zener barrier or galvanic isolator but at supply voltages above 16V the internal current limit will function and the audio output will be reduced Direct connection to supplies up to 28V of either polarity will not damage the sounder but it is recommended th...

Страница 2: ...R385 ATEX certificate specifies that the maximum permitted total capacitance that may be connected between the and terminals shall not exceed 83nF irrespective of the Zener barrier or galvanic isolator powering the sounder This total capacitance includes the cable capacitance plus the capacitance of any other connected device This should not be restrictive unless the sounder and the barrier or iso...

Страница 3: ...ol switch is in the positive supply or the power supply is being turned on and off only a single channel Zener barrier is required as shown in Fig 4 This circuit may also be used if the sounder is being controlled from the hazardous area by a mechanically activated switch complying with the requirements for simple apparatus as defined by EN 60079 11 i e having IP20 protection and able to withstand...

Страница 4: ... in which the first and second stage alarm tones are activated by the alarm outputs of a BA327E intrinsically safe loop powered indicator The BA327E alarm outputs have been certified as simple apparatus and may therefore be used to switch the BR385 sounder in the hazardous area The contacts of most certified intrinsically safe relays may also be used in the same way Fig 8 Loop powered BA327E intri...

Страница 5: ...1s OFF Alternating 544Hz 100ms 440Hz 400ms NFS 32 001 Motor Siren Slow rise to 1200Hz Motor Siren Slow rise to 800Hz Continuous 1200Hz Motor Siren Slow rise to 2400Hz Intermittent 1000Hz 1s ON 1s OFF Sawtooth 1200 500Hz 1Hz D I N PFEER P T A P Intermittent 1000Hz 1s ON 1s OFF PFEER General Alarm 420Hz 0 625s Australian Alert 500 1200Hz 3 75s 0 25s Australian Evacuate 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 ...

Страница 6: ...drogen when the terminals are connected to an isolated contact This is unlikely to be restrictive Uo is unlikely to reduce the permitted cable capacitance when the terminals are connected to a diode return barrier or galvanic isolator in the safe area but Io should be considered when determining the maximum permitted cable inductance but again is unlikely to be restrictive APPENDIX 2 IECEx certifi...

Отзывы: