Page9
Selecting memorisation of Main Alarm
According to the type of installation, you can select the activation or deactivation of the Main Alarm Latching.
By selecting the Latching function, the relay remains closed until the RESET button is pressed.
By unselecting the Latching function, the relay won’t remains closed when the alarm stops.
Note. The memorisation is subdivided in three ways:
1) Memorisation of single zone
2) Memorisation of first zone
3) Memorisation of second zone
Selectio n
Use the UP and DOWN buttons to select Latching (memorization).
Each time you press “ENTER” the ON/OFF message is changed.
In the “ON” position, the latching function is enabled.
In the “OFF” position, the latching function is disabled.
Once you have selected it, use the UP and DOWN buttons to move to the next selection.
Selecting the functioning mode of the Main Alarm Relay
According to the type of installation, you can select the relay functioning mode.
The relay functioning modes are two: continuous and impulse.
In the “Continuous” position, the relay remains closed until the alarm status continues, or until the alarm
stops.
In the “Impulse” position, the relay remains closed for 20 seconds, and then disenergizes afterwards.
Selectio n
Use the UP and DOWN buttons to select Relay.
Each time you press “ENTER” the Continuous/Impulse message is changed.
Once you have selected it, use the UP and DOWN buttons to move to the next selection.
Selecting the Positive Safety
According to the type of installation, you can select the Positive Safety function.
Selectio n
Use the UP and DOWN buttons to select Positive Safety.
Each time you press “ENTER” the ON/OFF message is changed.
In the “ON” position, the Positive safety function is enabled.
In the “OFF” position, the Positive safety function is disabled.
Once you have selected it, use the UP and DOWN buttons to move to the next selection.
General Functions
Giù
Sù
SX
DX
ENTER
Relay: Continuous
Impulse
Positive Safe: ON
OFF
Latch Zone 1: ON
OFF
Latch Zone 2: ON
OFF