Page 12
Use the UP and DOWN buttons to select Print, and press “ENTER”.
Now you can print the following:
The events on the current state of the BX308xp for all probes.
All the events in the datalogger.
Select arrow and press “Enter”
to return to the Menu.
Select arrow and press “Enter” to return to the Menu.
Test Conventional Probes
Use the UP and DOWN buttons to select Test Probes, and press “ENTER”.
Check voltage of probes
This screen is used by technicians to check the voltage detection state compared to the room gas concentration.
The cursor goes on probe 1. The voltage and current detected by the probe are shown.
To read other probes, use the RIGHT and LEFT buttons to reach the desired probe.
General Functions (continue)
Giù
Sù
SX
DX
ENTER
Print status
Print datalogger
1 2 3 4 5 6 7 8
T * T T * * E E
1 2 3 4 5 6 7 8
T T T T E E E E
Zone 1
Zone 2
V. 3,2 I=20,2 mA
BEINAT
== BX308/xp ==
Ver: 1.0 S/N Sample
Serial number:
0102
Date Hour
07/oct/17 10:00
State probes
------------- ------------
Probe 01 Zone 1
Gas Type: Explosive
Gas Level: 02.9 LEL
Meas.Current: 06.2 mA
Status: Normal
------------- ------------
Probe 02 Zone 1
Disabled
------------ ------------
Probe 03 Zone 1
Disabled
------------- ------------
Probe 04 Zone 1
Disabled
------------- ------------
Probe 05 Zone 1
Disabled
------------- ------------
Probe 06 Zone 1
Disabled
BEINAT
== BX308/xp ==
Ver: 1.0 S/N Sample
Serial number:
0102
Date Hour
07/oct/17 10:00
Datalogger
------ ----------- ------
- Event 01 -
06/jun/2010 08:27
Reset
------------ ------------
- Event 02 -
07/jun/2010 10:11
Hard Reset
------------ ------------
- Event 03 -
07/jun/2010 10:27
Vbat=11.8V
------ ---------- ------
- Event 04 -
07/jun/2010 11:27
Black-out
------------ ------------
-Event 05-
06/jun/2010 09:27
Probe 16 Fault
V=00.1 V I=01.1 mA