“精锐”压缩冷凝机组 

“SLIM POWER”CONDENSING UNIT 

 

 

   

   

   

冷(无

  

锡)有

   

   

   

 

Beijer Ref (Wuxi) Co. Ltd 

PN: 

YAL0002-60 

Issue: 

Date:      01/01/20 
Page:       25 of 26  
EN: 

 

 

 

 

25 

 

5

、冷风机结霜

 

5

Evaporator frosting

 

除霜

 

Defrost and clean evaporator

 

6

、冷风机风机故障

 

6

Evaporator fan fault

 

修理或更换

 

To be rectify and change fan if required

 

7

、机组选型偏小

 

7

Unit capacity 

shortage

 

增加设备

 

Add unit

 

8

、机组处于保护状态

 

8

Unit is protected

 

排除故障并复位

 

Troubleshooting and resetting 

频繁启动

 

Compressor start frequently

 

1,

、缺少制冷剂

 

1

Lack refrigerant 

查找泄漏并维修后重新充注制冷剂

 

Check leakage and repair, charge refrigerant

 

2

、管路堵死

 

2

Line blocking

 

查找原因并更换必要部件

 

To be rectify and change part if required

 

3

、机组处于保护状态

 

3

Unit is protected

 

查找原因,复位,并重新运行

 

To be rectify , reset and restart

 

4

、冷风机失效

 

4

Evaporator failure

 

查找原因,修理后重新启动

 

To be rectify , repair and restart

 

5

、压缩机失效

 

5

Compressor failure

 

维修压缩机,必要时更换压缩机

 

Maintenance compressor and change compressor if required

 

 
 
 
 
 

6

、保修条件

Warranty

 

保修条件请参照销售合同约定或咨询公司销售代表!

 

Please refer to the terms of the sale contract or the consulting company sales representative

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание SLIM POWER

Страница 1: ...01 20 Page 1 of 26 EN Beijer Ref Wuxi Co Ltd SLIM POWER Condensing Unit Installation Instructions 2 0 7 5HP For 2 0 7 5HP THANK YOU FOR CHOOSING THE BEIJER CONDENSING UNIT TO ENSURE TROUBLE FREE INSTA...

Страница 2: ...Compressor Start Up Reset 5 1 4 Caution Compressor 6 1 5 Personal Protective Equipment 6 1 6 Refrigerant Reclaim 6 1 7 No Smoking 6 1 8 Caution Unit Pressurized 6 1 9 Caution Refrigerant Type 7 1 10 C...

Страница 3: ...p Vacuum 11 2 1 9 Lubrication 11 2 1 10 Unit maintenance 12 2 1 11 Compressor Crankcase heater 12 2 1 12 Unit Electrical Connection 12 2 2 Refrigeration Piping 13 2 3 Compressor Starting 14 2 4 Fan Sp...

Страница 4: ...2 60 Issue D Date 01 01 20 Page 4 of 26 EN 4 4 WIRING SCHEMATIC DIAGRAMS 20 4 1 SLIM POWER Unit MT LT standard 20 4 2 SLIM POWER Unit LT with control panel 21 4 3 Coresense SLIM POWER Unit LT with Cor...

Страница 5: ...carry out all electrical work Always isolate the power to the unit before checking and or diagnosing the units Never work on any electrical item without isolating or disconnecting the power supply Al...

Страница 6: ...or discharge pipe temperature is high anything contacted may reach the ignition point to fire Leaking refrigerant please pay attention to the protection of the eyes and skin When removing refrigerant...

Страница 7: ...se ONLY POE oil do NOT mix POE with other oils when using refrigerants R404A 1 11 Caution Sharp Edges All units are manufactured with sheet metal thus this process had been taken to ensure the edges a...

Страница 8: ...scroll compressor which are fitted with inherent internal line break motor protection After opening the protector may not reset for several hours until the motor cools sufficiently Scroll compressors...

Страница 9: ...range with refrigerant R22 evaporating temperature is from 10 to 10 Low temperature range X series units with refrigerant R404 R22 evaporating temperature is from 40 to 20 Low temperature range N seri...

Страница 10: ...ion to the condenser Condensing Unit should be properly installed on horizontal base with corresponding foot bolts The liquid sight glass is located inside the unit Allow sufficient space around the a...

Страница 11: ...positive pressure region When the unit is installed in a cold ambient the cut out pressure shall be lower than the pressure corresponding to the ambient temperature 2 1 6 Warning Reset Motor Protect W...

Страница 12: ...e oil temperature Oil temperature should be higher than the ambient temperature for at least 10K The expected temperature would be between 50 70 Recommend to check oil temperature regular for ensure t...

Страница 13: ...the rotation of the valve rod After turning valve rod lock the gland nut with a torque wrench for 13 torque to prevent leakage of refrigerant The detail is below Unit Model Gland Nut Torque N m BD020M...

Страница 14: ...efrigerant velocity to ensure efficient oil return Horizontal suction lines shall slope towards to the units to allow the oil return freely to the compressor by gravity A 1 100 slope is considered suf...

Страница 15: ...t in particular blended zeotropic refrigerant such as R404A require proper procedures to be observed Initially charge 60 to 80 of the expected refrigerant charge in liquid form into the liquid receive...

Страница 16: ...rom its mounting place the following procedures need to be carried out professionally by qualified personnel Failure to do so may result in personal injury or death property damage by fire or explosio...

Страница 17: ...the warranty Refer to the Standard Terms Conditions of Sale in the Price Guide for warranty statements Continuous product improvement is our company policy Beijer Ref reserves the right to make change...

Страница 18: ...Take the necessary measures to avoid the ponding damage to the unit 3 Space around unit should be enough for easy ventilation and daily maintenance for specific dimension please refer to 3 2 4 For a...

Страница 19: ...Page 19 of 26 EN 19 BDN040LZ2 D F BDN040LZ2 D 585 388 1032x425x845 BDN050LZ2 D F BDN050LZ2 D 585 388 1032x425x845 BDN060LZ2 D F BDN060LZ2 D 585 388 1032x425x845 BDN075LZ2 D F BDN075LZ2 D 585 388 1032x...

Страница 20: ...L N 1 13 14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 1 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 19 Dischare...

Страница 21: ...3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 6 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH AS...

Страница 22: ...14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 5 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH...

Страница 23: ...se phase 6 6 3 phase unbalance To be rectify and correct it 7 7 Compressor over current To be rectify and correct it 8 8 Discharge temperature is too high To be rectify and correct it 9 9 Compressor m...

Страница 24: ...2 2 Low superheat Adjust expansion valve 3 3 Evaporator frosting Defrost and clean evaporator 4 4 Evaporator fan fault To be rectify and change fan if required Abnormal noise from compressor 1 1 Comp...

Страница 25: ...ed Troubleshooting and resetting Compressor start frequently 1 1 Lack refrigerant Check leakage and repair charge refrigerant 2 2 Line blocking To be rectify and change part if required 3 3 Unit is pr...

Страница 26: ...Beijer Ref reserves the right to alter its products without notice more information please contact with sales and visit Beijer Ref website http www beijerref com cn Beijer Ref Wuxi CO LTD No 12 Xindu...

Отзывы: