再次检查现场布线及工厂端口接线。由于运送过程中的振动,工厂连接处可能会松动,保证合适的风叶转

向,使气流从盘管侧进入,从风扇电机侧排出,确保压缩机的曲轴箱加热器在初始启动之前和/或在关闭之后,
通电至少 12 小时。 
 

在系统成功启动之后,请检查: 

 

电流和电压水平, 

 

吸气过热度设置和排气温度, 

 

异常的管路振动, 

 

油位和制冷剂充注。 

Double  check  all  field  wiring  connections  and  factory  terminations.  Factory  connections  can 

vibrate loose during shipment. Ensure correct fan motor rotation,  airflow  is  induced  from  coil side 
and forced out of fan motor side. 

If  fitted,  ensure  that  the  crankcase  heater  has  been  energised  for  a  minimum  12  hours  before 

initial start-up and / or after prolonged shutdown periods. 

 
After the successful start up of the system, check: 
•  Current draw and voltage levels. 
•  Suction superheat settings and discharge temperatures. 
•  Abnormal refrigeration piping vibrations. 
•  Oil level and refrigerant charge. 

 

 

2.5.2 

警告

—拆卸

Warning

 

Decommissioning 

 

对于机组从安装的地方拆除,需要专业技术人员按照一定的程序来进行。假如不按步骤进行的话可能
引起机组失火或爆炸,这将导致人员的伤亡,财产损失。不允许把制冷剂直接排放到大气中。

 

In order to remove  the unit from its mounting place, the following procedures need to be carried out 
professionally by qualified personnel. Failure to do so may result in personal injury or death, property 
damage by fire or explosion. Discharge of refrigerant to atmosphere is illegal and may result in heavy 
fines by relevant regulatory authorities.

 

 

 

要把所有的制冷剂泵到储液器或适当的容器中(如回收桶),然后关闭相关阀门。所有不能重新使用的制
冷剂必须回收或者销毁;

 

 

切断电源,拆除所有现场的电线以及相关设备,最后拆除接地线;

 

 

由于机组和外界环境存在压差,在拆除制冷剂管道时要特别小心。系统的润滑油中存有少量的制冷剂,系
统中压力的升高使制冷剂不断的沸腾和汽化这对人会造成潜在的危害;

 

 

切割并密封液管和吸气管的连接处;

 

 

把机组从安装位置上搬走,需要适当的搬运设备。

 

 

Pump down the entire refrigerant charge into the liquid receiver or appropriate container such as 
reclaim  cylinder,  and shut  related valves.  All  reclaimed refrigerant  that  is  not  re-used must be 
taken  to  an  approved  refrigerant  recycling  or  destruction  facility.    Beijer  Ref  Branches  will 
accept the used refrigerant. 

 

Disconnect  the  power  supply.  Remove  all  necessary  field  electrical  wiring  and  related 
components, leaving the earth wire to the last. 

 

Care must be taken when disconnecting the refrigeration piping because of unbalanced pressure 
between the unit and ambient. There may be a small amount of refrigerant trapped in the oil, the 

Содержание SLIM POWER

Страница 1: ...01 20 Page 1 of 26 EN Beijer Ref Wuxi Co Ltd SLIM POWER Condensing Unit Installation Instructions 2 0 7 5HP For 2 0 7 5HP THANK YOU FOR CHOOSING THE BEIJER CONDENSING UNIT TO ENSURE TROUBLE FREE INSTA...

Страница 2: ...Compressor Start Up Reset 5 1 4 Caution Compressor 6 1 5 Personal Protective Equipment 6 1 6 Refrigerant Reclaim 6 1 7 No Smoking 6 1 8 Caution Unit Pressurized 6 1 9 Caution Refrigerant Type 7 1 10 C...

Страница 3: ...p Vacuum 11 2 1 9 Lubrication 11 2 1 10 Unit maintenance 12 2 1 11 Compressor Crankcase heater 12 2 1 12 Unit Electrical Connection 12 2 2 Refrigeration Piping 13 2 3 Compressor Starting 14 2 4 Fan Sp...

Страница 4: ...2 60 Issue D Date 01 01 20 Page 4 of 26 EN 4 4 WIRING SCHEMATIC DIAGRAMS 20 4 1 SLIM POWER Unit MT LT standard 20 4 2 SLIM POWER Unit LT with control panel 21 4 3 Coresense SLIM POWER Unit LT with Cor...

Страница 5: ...carry out all electrical work Always isolate the power to the unit before checking and or diagnosing the units Never work on any electrical item without isolating or disconnecting the power supply Al...

Страница 6: ...or discharge pipe temperature is high anything contacted may reach the ignition point to fire Leaking refrigerant please pay attention to the protection of the eyes and skin When removing refrigerant...

Страница 7: ...se ONLY POE oil do NOT mix POE with other oils when using refrigerants R404A 1 11 Caution Sharp Edges All units are manufactured with sheet metal thus this process had been taken to ensure the edges a...

Страница 8: ...scroll compressor which are fitted with inherent internal line break motor protection After opening the protector may not reset for several hours until the motor cools sufficiently Scroll compressors...

Страница 9: ...range with refrigerant R22 evaporating temperature is from 10 to 10 Low temperature range X series units with refrigerant R404 R22 evaporating temperature is from 40 to 20 Low temperature range N seri...

Страница 10: ...ion to the condenser Condensing Unit should be properly installed on horizontal base with corresponding foot bolts The liquid sight glass is located inside the unit Allow sufficient space around the a...

Страница 11: ...positive pressure region When the unit is installed in a cold ambient the cut out pressure shall be lower than the pressure corresponding to the ambient temperature 2 1 6 Warning Reset Motor Protect W...

Страница 12: ...e oil temperature Oil temperature should be higher than the ambient temperature for at least 10K The expected temperature would be between 50 70 Recommend to check oil temperature regular for ensure t...

Страница 13: ...the rotation of the valve rod After turning valve rod lock the gland nut with a torque wrench for 13 torque to prevent leakage of refrigerant The detail is below Unit Model Gland Nut Torque N m BD020M...

Страница 14: ...efrigerant velocity to ensure efficient oil return Horizontal suction lines shall slope towards to the units to allow the oil return freely to the compressor by gravity A 1 100 slope is considered suf...

Страница 15: ...t in particular blended zeotropic refrigerant such as R404A require proper procedures to be observed Initially charge 60 to 80 of the expected refrigerant charge in liquid form into the liquid receive...

Страница 16: ...rom its mounting place the following procedures need to be carried out professionally by qualified personnel Failure to do so may result in personal injury or death property damage by fire or explosio...

Страница 17: ...the warranty Refer to the Standard Terms Conditions of Sale in the Price Guide for warranty statements Continuous product improvement is our company policy Beijer Ref reserves the right to make change...

Страница 18: ...Take the necessary measures to avoid the ponding damage to the unit 3 Space around unit should be enough for easy ventilation and daily maintenance for specific dimension please refer to 3 2 4 For a...

Страница 19: ...Page 19 of 26 EN 19 BDN040LZ2 D F BDN040LZ2 D 585 388 1032x425x845 BDN050LZ2 D F BDN050LZ2 D 585 388 1032x425x845 BDN060LZ2 D F BDN060LZ2 D 585 388 1032x425x845 BDN075LZ2 D F BDN075LZ2 D 585 388 1032x...

Страница 20: ...L N 1 13 14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 1 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 19 Dischare...

Страница 21: ...3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 6 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH AS...

Страница 22: ...14 3 4 5 6 7 9 8 10 K1 N A1 A2 By Customer 12 2 NO COM L1 L2 L3 L1 Phase Alarm To K1 11 L2 L3 7 WS851 5 VER 00 UNIT S No Overload T1 2T1 4T2 6T3 A C LP HP D B T1 N C 95 96 17 18 20 Compressor 1 EARTH...

Страница 23: ...se phase 6 6 3 phase unbalance To be rectify and correct it 7 7 Compressor over current To be rectify and correct it 8 8 Discharge temperature is too high To be rectify and correct it 9 9 Compressor m...

Страница 24: ...2 2 Low superheat Adjust expansion valve 3 3 Evaporator frosting Defrost and clean evaporator 4 4 Evaporator fan fault To be rectify and change fan if required Abnormal noise from compressor 1 1 Comp...

Страница 25: ...ed Troubleshooting and resetting Compressor start frequently 1 1 Lack refrigerant Check leakage and repair charge refrigerant 2 2 Line blocking To be rectify and change part if required 3 3 Unit is pr...

Страница 26: ...Beijer Ref reserves the right to alter its products without notice more information please contact with sales and visit Beijer Ref website http www beijerref com cn Beijer Ref Wuxi CO LTD No 12 Xindu...

Отзывы: