5.4. Changing Parameters
TFT and OLED Display :
P2 01 P2 01 P2 01 P2 01 P2 01
Stop
P1-01
P1-08
30.0A
P1-08
Stop
15kW 400V 3Ph 50.0Hz
30.0A
P1-08
30.0
3.0 30.0A
15kW 400V 3Ph
Press and hold the
Navigate key > 2
seconds.
Use the up and down
keys to select the
required parameter.
Display will show the
present parameter
value on the lower
line of the display.
Press the Navigate
key for < 1 second.
Adjust the value using
the Up and Down
keys. Display will
show the maximum
and minimum possible
settings on the lower
line of the display.
Press for < 1 second
to return to the
parameter menu.
Press for > 2 seconds
to return to the
operating display.
5.5. Parameter Factory Reset / User Reset
Beijer BFI-P2 provides a feature to allow the user to define their own default parameter set. After commissioning all required
parameters, the user can save these as the default parameters by setting P6-29 = 1. If required, the User Default Parameters may be
cleared by setting P6-29 = 2.
If the user wishes to reload 'Factory Defaults' parameters to the drive memory, then follow the procedure shown below-left.
If the user wishes to reload their own pre-saved 'User Defaults' parameters to the drive memory, then follow the procedure shown
below-right.
Factory Parameter Reset, TFT and OLED Display :
User Parameter Reset, TFT and OLED Display :
P2 01 P2 01
P2 01
P2 01 P2 01 P2 01
Stop
P-Def
Stop
Stop
U-Def
Stop
15kW 400V 3Ph 50.0Hz
15kW 400V 3Ph
P1-08
30.0
3.0 30.0A
15kW 400V 3Ph
Press and hold the Up,
Down, Start and Stop
keys for >2s.
The display shows
P-Def. Briefly press the
Stop key.
The display returns to
Stop. All parameters
are reset to Factory
defaults.
Press and hold the Up,
Down and Stop keys
for >2s.
The display shows
U-Def. Briefly press
the Stop key.
The display returns to
Stop. All parameters
are reset to User
Defaults.
5.6. Resetting the Drive Following a Trip
Beijer BFI-P2 has many protection features, designed to protect both the drive and motor from accidental damage. When any of
these protection features are activated, the drive will trip, and display a fault message. The fault messages are listed in section
When a trip occurs, after the cause of the trip has been investigated and rectified, the user can reset the trip in one of the following ways:
Press the keypad Stop key.
Power off the drive completely, then power on again.
NOTE
Allow 30 seconds between power off and back on.
If P1-13 > 0, switch off digital input 1, then back on again.
If P1-12 = 4, reset via the fieldbus interface.
If P1-12 = 6, reset via CAN.