Additional Installation Tips

6.4 Ambient Temperature

The maximum ambient temperature for the operator panel is provided in the
specifications. The ambient temperature refers to the temperature in the device
cabinet which cools the panel’s electronics.

Operator
panel

Power

Power

Power

30 °C outside

Top
50 °C inside

Bottom
40 °C inside

Middle
45 °C inside

Airflow

Axial fan
120 x 120 mm

5354

In most cases, the ambient temperature for the operator panel is significantly
higher than the device cabinet’s ambient temperature.
If the cabinet is tall and there are a number of heat-generating devices, the
temperature at the top of the cabinet will be considerably higher than the
theoretical temperature increase that would be expected. All electronics are
sensitive to heat. The lifespan of an electrolytic capacitor is cut in half with an
8-10 °C increase in temperature. A 15-20 °C temperature increase results in a
quarter of the lifespan etc.
Rittal has a good program for estimating the anticipated average temperature in
the cabinet as well as a large program for controlling the temperature in the device
cabinet.
An enamel-coated steel cabinet has a radiant heat value of 5.5 W/m

2

and degrees

C.
Installing a fan inside the cabinet will even out the temperature, while moving air
provides considerably better cooling than still air. A suitable fan is a 120 x 120 mm
axial fan, available in 24 V DC, 115 and 230 V AC.
Install the fan so that it sits in the cooler area and blows cold air against the operator
panel. If the fan is mounted at the top and sucks warm air upwards, the fan’s
ambient temperature will be higher, resulting in a shorter lifespan.
A good fan with a ball-bearing mounting has an expected lifespan of at least
40,000 hours (not a guaranteed lifespan) at 40 °C. This corresponds to at least 4
years of continuous use. If a thermostat is installed, the fan only operates when
needed.
Large graphic terminals draw only one fifth of the current when the background
lighting is off. The loss effect drops from e.g. 25 W to only 5 W.
An approximate value of the net power consumption for the operator panel can
be calculated by multiplying the supply voltage with the current drawn by the
operator panel. This is assuming that all supplied power is transformed to heat.

Beijer Electronics, MAEN810D

21

Содержание EXTER K30m

Страница 1: ...EXTER K30m Installation Manual English MAEN810D 2014 10 ...

Страница 2: ... updating this publication Beijer Electronics AB assumes no responsibility for any errors that may appear in this document Read theentireinstallation manual prior to installing and using this equipment Only qualified personnel may install operate or repair this equipment Beijer Electronics AB is not responsiblefor modified altered or renovated equipment Because the equipment has a wide range of appl...

Страница 3: ...icalData 11 4 ChemicalResistance 12 4 1 MetalCasing 12 4 2 Screen and Overlay Material 12 4 2 1 Autotex F157 207 12 4 2 2 Screen Surface 13 4 2 3 Screen and Keyboard Protector 14 5 Operator Panel Drawings 15 5 1 Communication Ports 15 5 2 EXTER K30m Outline 16 5 3 EXTER K30m Text Strip 17 6 Additional Installation Tips 18 6 1 Grounding the Operator Panel 18 6 2 Ethernet Connection in the Panel 19 ...

Страница 4: ...sa powerful irritant Incase of skincontact wash immediately with plenty ofwater In case of eye contact holdthe eye open flush with plenty of water and get medical attention The figures in this manualserves an illustrative purpose Because of the many variables associated with any particular installation the supplier cannot assume responsibility for actual use based onthe figures The supplierneither gu...

Страница 5: ...EREUSE This product contains a battery this must onlybe changedin an areaknown tobe non hazardous Replace the battery with aCR2450 battery Use of anothertype ofbattery maypresent a risk offire orexplosion Warning Battery may explode if mistreated Do not recharge disassemble or dispose of in fire LA BATTERIEPEUT EXPLOSEREN CAS DE MAUVAISE MANIPULATION NE LA RECHARGEZ PAS NE LA DÉMONTEZ PAS ET NE LA ...

Страница 6: ...e product to the poweroutlet Peripheral equipment must be appropriate forthe application and location 1 4 During Use Keep the operatorpanel clean Emergency stopand othersafety functions may notbe controlled from the operator panel Do not use excessive force orsharpobjects 1 5 Service and Maintenance Onlyqualified personnel shouldcarry outrepairs The agreed warranty applies Before carryingout any cl...

Страница 7: ...ch 7 36 inch 202 mm 100 mm 4 0 inch 7 95 inch 2 24 inch Caution The openings on the enclosure are for airconvection Do not cover these openings 2 2 Installation Process 1 Unpackand check the delivery If damage isfound notify the supplier x 7 Panel cut out 166 x 149 mm 6 54 x 5 87 inch Note Place the operator panelon a stable surface duringinstallation Dropping it or letting itfall may cause damage...

Страница 8: ...uated draw along the outer sides ofthe holesandcutaccording to the markings For text strip 7 0 mm 14 0 mm 0 55 inch 0 28 inch 3 Secure the operator panel in position usingallthe fasteningholesand the provided brackets and screws x 7 0 5 1 0 Nm Beijer Electronics MAEN810D 8 ...

Страница 9: ...ise errors in communication may occur Ensure that the voltage and polarity of the powersource is correct Separate high voltage cables from signal and supply cables Shielded communication cables are recommended 24V DC RS422 RS485 RS232 24V DC A D Controller Power C B Ethernet Connect cable A Connect cable B usingan M5 screwand agroundingconductor asshort as possible thatissized correctly accordingt...

Страница 10: ...nections to the Controller For information aboutthe cables to be used when connecting the operator panelto the controller please refer to the helpfile for the driverin question 2 2 3 Other Connections and Peripherals Cables peripheral equipment and accessories must be suitable forthe application and itsenvironment Forfurtherdetailsor recommendations please refertothe supplier Beijer Electronics MAE...

Страница 11: ...at 25 C Temperature coefficient 0 034 0 006 ppm C2 Real time clock battery CR2450 UL and cUL Sanyo or Panasonic Minimum lifetime 3 years Power consumption at rated voltage Normal 0 15 A Maximum 0 35 A Display FSTN LCD 240 x64 pixels monochrome transflective LED backlight lifetime at the ambient temperature of 25 C 35 000 h Active area of display W xH 127 0 x 33 8 mm Fuse Internal DC fuse 2 0 AT 5 ...

Страница 12: ...d 3 Hydrochloric acid 5 Nitric acid 10 Isopropyl alcohol Phosphoric acid 43 Na hypochlorite 10 Turpentine Note If exposure to any of the above chemicals is demanded itis recommended to first test the chemical in a hidden spot of the metal casing The powder paint shows little or no resistance to the followingchemicals at room temperature Acetic acid conc Methyl ethyl ketone Toluene Acetone Nitric a...

Страница 13: ...ffin oil Windex1 Cyclohexanol Persil powderin solution1 Wisk Diacetone alcohol Petroleum spirit1 1 Extremely faintglossingof the texture was noted Autotex withstands DIN 42 115 Part2 exposure of up to 1 hour duration to glacial aceticacid without visible change Autotex is not resistant to high pressure steam at over 100 C orthe following chemicals Concentrated mineral acids Benzylalcohol Concentra...

Страница 14: ...d Protector For harsh environments and exposure tooutdoorconditions it isrecommended to use a protective film toguardthe screen and the keyboard from damage These optional parts canbe ordered from BeijerElectronics Beijer Electronics MAEN810D 14 ...

Страница 15: ...Operator PanelDrawings 5 Operator Panel Drawings 5 1 Communication Ports RS 232 RS 422 RS 422 485 RS 485 Ethernet USB Beijer Electronics MAEN810D 15 ...

Страница 16: ...Operator PanelDrawings 5 2 EXTER K30m Outline Beijer Electronics MAEN810D 16 ...

Страница 17: ...Operator PanelDrawings 5 3 EXTER K30m Text Strip 4 5 19 75 20 5 20 5 20 5 20 5 20 5 19 75 179 Text max 18 5x8 0 Text max 17 0x8 0 10 75 9 Beijer Electronics MAEN810D 17 ...

Страница 18: ...raid between the panel s chassis and the closest groundingpoint on the door see 3 in drawingabove 3 Connect astrongbut shortgroundingbraid betweenthe doorand the device cabinet see 4 indrawingabove 4 Twist the cables onto the 24 V DC feed see 5 in drawingabove 2 turns around the ferrite core provide 4 times the suppressionof1 turn 3 turns around the ferrite core provide 9 times the suppressionof1 ...

Страница 19: ...unithas its shield directly grounded or groundedviaa capacitor Note In many cases connecting the shielded Ethernet cabling to the chassis at both ends is inappropriate Hum or grounding loops canoccur Unshielded cabling may even result in fewer communication errors A good solutionmay be touse a shielded Ethernet cable but toconnect the shield at one end only One option istobreak the shield see 3 in...

Страница 20: ...he shield to the ground via a 0 1 µF 250 Vplastic capacitor Both ends are then connected tothe ground in terms ofHF but only connected to the ground at one end in terms ofLF thus avoidingthe 50 Hz groundingloops Metal cabinet Metal cabinet Terminal or connector Terminal or connector EMC cable gland Plastic cable gland Shielded cable Shielded cable Short distance Cable clamp in steel 5353 1 Use an ...

Страница 21: ... a large program for controllingthe temperature in the device cabinet An enamel coated steel cabinethasaradiant heatvalue of 5 5 W m2 and degrees C Installinga fan inside the cabinetwill even out the temperature while moving air providesconsiderably better coolingthan stillair Asuitable fan is a120 x120 mm axialfan available in 24 VDC 115 and 230 V AC Install the fan so that it sitsin the cooler a...

Страница 22: ...ELVaccording to EN 60950 protection against electric shock andUL 950 Note Here is an example that explains why a secure 24 V DC feed can be ruined by mixing 24 V relay contacts with 230 V AC relay contacts in a smaller controller Check that the clearances and creepage distances between 24 V DC and 230 V AC fulfill EN 60950 or UL 950 If not input a separate 24 V unit into the operator panel If ther...

Страница 23: ...USB memory stick keyboard or similardevice is plugged in If anumberofunitsare connectedthat have a0 Vand a groundconnection and these are connected to various groundingpoints there is a substantial risk of problems Groundingcurrents go through communication cables the rearplate of the controller andinternally in the operatorpanel and can cause errors Use external units to improve communication and...

Страница 24: ...ires may be onthe same levelor require pull up orpull downtoensure that no faultysignals are detected when the busisin restingmode all transmittersare disconnected 1 2 3 4 5 V 0 V 1 K 1 K 120 ohm 120 ohm 120 ohm 5 V 5 V 0 V 0 V 0 V 0 V 0 V 0 V 1 K 1 K 1 K 1 K VCC VCC 120 ohm Inside operator panel Operator panel RS422 CAB8 CAB8 Bus RS485 Shield Bus termination 5358 2 14 15 6 19 7 8 1 2 3 4 5 6 7 8 ...

Страница 25: ...Head office Beijer Electronics AB Box 426 201 24 Malmö Sweden www beijerelectronics com 46 40 358600 ...

Отзывы: