5.15 Control of BFI by CANopen
BFI-E3 should have firmware version 3.08 (from August 2019) for full functionality. Eds-file to
be used for BFI-E3 is called
BFI-E3_Ver31.eds
or later and is to be downloaded from
www.beijerelectronics.
BFI-E3 IP20 has one RJ45 port for CANopen and BFI IP66 has two parallel RJ45 ports.
Settings in BFI are Station number 1 and 500 kbit/sec.
Hardware
Function
Comment
CAB 154
3 m shielded cable with one RJ45 for BFI and one
9-pole D-sub for X2 panels.
Built-in 120 ohm resistor in D-sub between
CANopen- pin1 and pin2.
CAB 155
Shielded 3 m cable with one RJ45 and 3 wires for
screwterminals marked H(+), L(-) and Shield.
120 ohm resistor for bus termination included.
OPT-2-J45SP-BFI
T-Connection of 2 serial cables into one drive.
RJ45 male to BFI and 2 female RJ45 for network
OPT-2-RJTRM-BFI
RJ45 with a 120 ohm resistor.
To be put in the last BFI-splitter.
Para-
meter
Name
Default
settng
Recommended
setting
Function
P-12
Command Source
0
7
7= Control by CANopen och ramptime in P-03 and P-04.
8= Control by CANopen och ramptime sent by CANopen.
P-14
Parameter Access
0
201
201 = Parameters above P-14 accessable.
P-24
Fast Deceleration time
0
Fast Deceleration ramptime from 0 to 50 Hz.
P-25
Analog Output Funct.
8
13: Analog output controlled via fieldbus
P-36
Communication
Setting
(Power off/on
when parameter has
been changed)
CANopen
1,
500 k,
3000
500 kbit/sec
3 settings in one parameter.
- Stationnumber 0-63. First Drive should be stationnumber 1.
- Communication speed, 125-1000 kbit/sek.
- Communication timeout. 0 = No timeout [msec].
2
1
DI1:
Startsignal
+24 VDC
DI1 must always be closed to start
BFI
IP66
CAB 154
Patchcable
Cat 6
CANopen master
X2 control HMI
CAB 155
RS485 + Pin1
OPT-2-
RJTRM-
BFI
OPT-2-
J45SP-BFI
RS485
– Pin6
GND Pin5
CANopen master
Nexto Xpress
CAN H
CAN-L
GND
BFI
IP20