background image

 

Beijer Electronics Frequency Inverter BFI-E3

               

KI00369C  2021-09 

 

 

 

 

www.beijer.se www.beijer.no

 

www.beijer.dk

 

www.beijerelectronics.de  www.beijerelectronics.com www.beijerelektronik.com.tr

       

17 (28)

 

5.14 Control of BFI by Modbus RTU  

BFI IP20 has one RJ45 port for Modbus RTU and BFI IP66 has two parallel RJ45 ports. A 
Modbus RTU network with BFI-E3, BFI-H3 or BFI-P2 is connected as below: 

 

 

 

 

 

 

 

 

                                     Settings in BFI are 115 200 bit/sec, 8 data bits, 1 stop bit, No Parity. 

 

Hardware 

Function 

Comment 

CAB 114 

Shielded cable with one RJ45 and 3 wires 

marked SDA, SDB and SG for 

screwterminals.   

Cable length 3 m. Modbus RTU- pin7 and  Modbus RTU+ 

pin8 in BFI.  

CAB 113 

Shielded cable with one RJ45 for BFI and one 

9-pole D-sub for X2 panels.   

Cable legth 3 m. Built-in 120 ohm resistor in D-sub 

between pin7 and pin8.  

OPT-2-J45SP-BFI 

T-Connection of 2 cables into one BFI IP20.     RJ45 to BFI and 2 female RJ45 for network connection 

OPT-2-RJTRM-BFI 

RJ45 with a 120 ohm resistor.  

To be put in the last BFI-splitter. 

 

 

Para- 

meter 

Name 

Default 

settng 

Recommended 

setting 

Function 

P-12 

Command Source 

3= Control by Modbus RTU and ramptime in P-03 and P-04. 

4= Control by Modbus RTU and ramptime sendt by Modbus. 

P-14 

Parameter Access 

201 

201 = Parameters above P-14 accessable. 

P-24 

Fast Deceleration time 

 

Fast Deceleration ramptime from 0 to 50 Hz. 

P-25 

Analog Output Funct. 

 

13: Analog output controlled via fieldbus 

P-36 

Communication 

Setting 

(Power off/on 

when parameter has 

been changed)

 

Modbus 

115,2k 

3000 

115,2k 

3 settings in one parameter. 

- Stationnumber 0-63. First Drive should be stationnumber 1. 

- Communication speed, 115,2=115.200 bits/sec. 

- Communication timeout. 0 = No timeout [msec]. 

 

2

 

1

 

DI1: 

Startsignal

 

+24 VDC

 

 

DI1 must always be closed to start 

Modbus master RTU 

 

SG

 

SDB

 

BFI

 

RDB

 

SDA

 

RDA

 

Put termination switch in 120 
ohms

 

1           8 

BFI 
IP66

 

CAB 113

 

Patchcable 
Cat 6

 

Modbus master 
X2 HMI

 

CAB 114

 

RS485 + Pin1

 

OPT-2-
RJTRM-
BFI

 

OPT-2-
J45SP-BFI

 

RS485 

– Pin6

 

GND       Pin5

 

Modbus master 
Nexto Xpress

 

D+  

 

D-

 

GND    

 

BFI 
IP20

 

Содержание BFI-E3 Series

Страница 1: ...ter turning off the supply Ensure correct earthing connections The earth cable must be sufficient to carry the maximum supply fault current which normally will be limited by the fuses or MCB Suitably...

Страница 2: ...ENT LIMIT CONTROL 16 5 13 TUNING OF PM MOTOR 16 5 14 CONTROL OF BFI BY MODBUS RTU 17 5 15 CONTROL OF BFI BY CANOPEN 18 5 16 CONTROL OF BFI BY MODBUS TCP 19 5 17 PI CONTROL 20 5 18 ENERGY OPTIMIZATION...

Страница 3: ...160 109 162 5 123 83 50 5 5 10 1 0 0070 0105 1 5 2 2 kW 0041 0095 1 5 4 0 kW 2 221 207 137 209 5 3 150 110 63 1 7 0153 4 0 kW 0140 0240 5 5 11kW 3 261 246 247 6 175 131 80 3 2 No 0300 0460 15 22kW 4 4...

Страница 4: ...3 310 210 238 252 197 7 0 Does not exist 0300 0460 7 5 11 kW 0300 0460 15 22 kW 4 360 240 275 300 227 9 5 NOTE 1x230 BFI E3 0070 and 3x400 V BFI E3 0041 are without brake transistor for Size 1 2ize2 w...

Страница 5: ...C Max Motor Cable Length Power losses Amps Amps mm2 Amps Amps mm2 m W 0 75 0022 3 5 6 1 5 1 5 2 2 1 5 100 22 5 1 5 0041 5 6 6 1 5 1 5 4 1 1 5 100 50 2 2 0058 7 5 10 1 5 1 5 5 8 1 5 100 50 4 0095 11 5...

Страница 6: ...beijerelektronik com tr 6 28 4 5 Installation of power supply grounding and motor cable IP66 Frame Size 1 IP66 Frame Size 2 4 A Incoming Power Connections B Motor Connections C Control Terminal Conne...

Страница 7: ...e an EMC gland is to be used Shield of motor cable is to be connected to ground terminal in the drive itself For IP20 drives the shield can be connected to the Protective earth terminal or clamped to...

Страница 8: ...be used together with a slow external overload protection and P34 2 Table shows setting current of the external overload protection Drive model Minimum resistance when regenerated power is equal with...

Страница 9: ...rward or Reverse This could typically be for Hand Off Auto applications also known and Local Remote for HVAC and pumping industries Switch Position Parameters to Set Notes P 12 P 15 Run Reverse STOP R...

Страница 10: ...DI1 active if terminal 24V Switches doesn t effect DI1 Parameter P 64 Input and Conditions Function DI1 Terminal 2 0 24 V OR Run Fwd OR Run Rev Active 1 24 V Active 2 24 V OR Run Fwd Active 3 24 V AND...

Страница 11: ...f the BFI is being used Picture below shows an overview of control signals for the drive and factory set functionality when an external 24 VDC is being used 2 3 4 5 6 7 1 DI1 Start signal DI2 Fwd or R...

Страница 12: ...110 overload Spin start variable torque P 14 Parameter Access 0 201 Normally only parameters P 01 to P 14 are accessable All other parameters are accessable with this P14 201 P 17 Switching Frequency...

Страница 13: ...DC Sign decides rotationdirection 4 to 20mA Trip if signal level 3mA 4 to 20mA Stop and Trip if signal level 3mA 20 to 4mA Trip if signal level falls 3mA P 20 Preset Speed 1 5 0 Hz Can be set between...

Страница 14: ...n 1 2 Motor accelerete to minimal frequency P 02 at start 3 Motor accelerete to latest speed before stop 5 5 Start stop by individual signals Start is done by a pulse on one terminal and stop on a sec...

Страница 15: ...0 to P 01 Hz 9 Output Motor Current 0 200 0 10V 0 to P 08 10 Motor Power 0 to 200 0 10V 0 to Rated inverter power kW 11 Load current 0 200 0 10V 0 till P 08 Current used producing torque on motor shaf...

Страница 16: ...ning is done measured values are stored in parameter P 55 P 56 and P 57 Auto tuning only needs to be done once If motor creates strange sound weak torque performance and speed is not stable change Gai...

Страница 17: ...connection OPT 2 RJTRM BFI RJ45 with a 120 ohm resistor To be put in the last BFI splitter Para meter Name Default settng Recommended setting Function P 12 Command Source 0 3 3 Control by Modbus RTU...

Страница 18: ...BFI T Connection of 2 serial cables into one drive RJ45 male to BFI and 2 female RJ45 for network OPT 2 RJTRM BFI RJ45 with a 120 ohm resistor To be put in the last BFI splitter Para meter Name Defau...

Страница 19: ...e IP address Para meter Name Default settng Recommended setting Function P 12 Command Source 0 7 7 Control by CANopen och ramptime in P 03 and P 04 8 Control by CANopen och ramptime sent by CANopen P...

Страница 20: ...al Setpoint 0 0 Digital Preset PI Setpoint in P 45 1 Analog Input 1 Terminal 6 PI setpoint P 45 PI Digital Setpoint 0 0 When P 44 0 PI setpoint for PI Controller P 46 PI Feedback Source Select 0 0 0 A...

Страница 21: ...top 5 20BFI Smartstick Communication between BFI Drive and PC software BFI Tools or app BFI Tools Mobile is done by Bluetooth through BFI Smartstick Bluetooth is not built into BFI but in BFI Smartsti...

Страница 22: ...2 seconds Press and hold the Navigate key 2 seconds To reset parameter values to their factory default settings press and hold Up Down and Stop buttons for 2 seconds The display will show Drive is ena...

Страница 23: ...P0 16 Heatsink Temperature Log 20 120 C 8 most recent values prior to trip updated every 30s P0 17 Motor Current 0 to 2x rated current 8 most recent values prior to trip updated every 256ms P0 18 DC...

Страница 24: ...gammable Relay single pole Maximum load 6 0 A with 230 V or 5A with 30 VDC Analog output 1 x User selectable Digital or Analog Output 0 10 V DC Maximum current 20 mA 10 bit Communication Modbus RTU or...

Страница 25: ...equipment EEE please contact your dealer or supplier for further information For disposal in countries outside of the European Union If you wish to discard this product please contact your local autho...

Страница 26: ...ms blockages or mechanical faults exist 5 Hardware Over Current Check the wiring to motor for phase to phase and phase to earth short circuits Disconnect motor and cable Retest If the drive trips with...

Страница 27: ...vided 26 Output fault Indicates a fault on the output of the drive such as 1 phase missing motor phase currents not balanced Check the motor and connections 41 Auto tune Fault The motor parameters mea...

Страница 28: ...Beijer Electronics Frequency Inverter BFI E3 KI00369C 2021 09 www beijer se www beijer no www beijer dk www beijerelectronics de www beijerelectronics com www beijerelektronik com tr 28 28...

Отзывы: