Technical data, mounting, wiring
PS2001-2410-0000
14
Version: 1.0
3.4
Output
Output voltage
Nom.
24V
Adjustment range
Min.
24-28V
Guaranteed value
Max.
30.0V
This is the maximum output voltage that can occur in the end position of the po-
tentiometer in clockwise direction due to tolerances. It is not a guaranteed
value that can be achieved.
Factory settings
Typ.
24.1V
±0.2% at full load (cold device)
Line regulation
Max.
10 mV
Between 85 and 300Vac
Load regulation
Max.
50 mV
Between 0 and 12A, static value, see Fig.
Output voltage over output current,
typ.
Residual ripple and ripple
voltage
Max.
50mV
ss
Bandwidth 20 Hz to 20 MHz, 50 Ohm
Output current
Nom.
12A
1)
At 24V and an ambient temperature below 45°C, see Fig.
Output current over
ambient temperature
Nom.
10A
At 24V and 60°C ambient temperature, see Fig.
Output voltage over output cur-
rent, typ.
Nom.
7.5A
At 24V and 70°C ambient temperature, see Fig.
Output current over ambient
temperature
Nom.
10.3A
1)
At 28V and an ambient temperature below 45°C, see Fig.
Output current over
ambient temperature
Nom.
8.6A
At 28V and 60°C ambient temperature, see Fig.
Output voltage over output cur-
rent, typ.
Nom.
6.45A
At 28V and 70°C ambient temperature, see Fig.
Output current over ambient
temperature
Typ.
30A
For at least 12ms once every five seconds, see Fig.
Dynamic output current ca-
pacity, typ
. The output voltage remains above 20V.
See chapter on
for further peak current mea-
surements. For AC 100V networks the pulse length is shorter than 12ms.
Overload behavior
Continuous cur-
rent
Output voltage > 13Vdc, see Fig.
Output voltage over output current, typ.
Hiccup mode
2)
Output voltage < 13Vdc, see Fig.
Output voltage over output current, typ.
Short circuit current
Min.
12.5A
3)
Load impedance <45mOhm, see Fig.
Short circuit at output, hiccup mode, typ.
Max.
15.5A
3)
Load impedance <45mOhm, see Fig.
Short circuit at output, hiccup mode, typ.
Max.
5A
RMS value of current, load impedance 50mOhm, see Fig.
Short circuit at out-
put,
Hiccup mode, typ.
Min.
28A
Up to 12ms, load impedance <45mOhm, see Fig.
Dynamic output current ca-
pacity, typ
.
Typ.
30.5A
Up to 12ms, load impedance <45mOhm, see Fig.
Dynamic output current ca-
pacity, typ.
Output capacity
Typ.
4 400μF
Included in the power supply
1)
Extra Power
This continuous power / current is permissible up to an ambient temperature of +45°C. Above +45°C, use
this power / current for a maximum duty cycle of 10%, i.e. no more than 1 minute every 10 minutes.
2)
Hiccup mode
In the event of heavy overload (when the output voltage drops below 13V), the power supply provides
continuous output current for 2s. The output is then switched off for about 18 seconds before a new switch-
on attempt is automatically made. This cycle is repeated as long as the overload persists. After the overload
has been rectified, the device will operate normally. See Fig. Short circuit at output, hiccup mode, typ.
3)
The discharge current of the output capacitors is not included.