Technical data, mounting, wiring
PS2001-2410-0000
13
Version: 1.0
3.3
Input inrush current
Active inrush current limitation (NTCs that are bridged by a relay contact) limits the inrush current after the
input voltage is switched on.
The charge current of the interference suppression capacitors during the first few microseconds after
switching on is not taken into account.
AC 100V
AC 120V
AC 230V
Input inrush
current
Max. 11A
peak
7A
peak
11A
peak
At +40°C, cold start
Typ. 9A
peak
6A
peak
6A
peak
At +25°C, cold start
Typ. 9A
peak
6A
peak
9A
peak
At +40°C, cold start
Inrush energy
Max. 0.1A²s
0.1A²s
0.4A²s
At +40°C, cold start
Fig. 4: Typical switch-on behavior at nominal load, 120Vac input voltage and 25°C ambient temperature
Fig. 5: Typical switch-on behavior at nominal load, 230Vac input voltage and 25°C ambient temperature