Access Rights
Description
Change Password
Users can change their password.
Download Safe Logic Data
The user can load the safety-related program onto the EL6910, EJ6910 or
EK1960.
Download Mapping Data
The user can load the mapping data for inputs, outputs, FBs etc. onto the
EL6910, EJ6910 or EK1960.
Download Safe User Data /
Replacement Values
The user can change safe user parameters on the EL6910, EJ6910 or
EK1960 and also change and load safe substitute values
Download Info Data
The user can activate and load the info data for connections and FBs on
the EL6910, EJ6910 or EK1960.
Download Project Data in
Restore Mode
The user can perform a restore. Not currently supported.
Activate / Deactivate Groups
The user can execute Customizing (enable and disable TwinSAFE groups)
on the EL6910, EJ6910 or EK1960.
4.8
Backup/Restore
Following the exchange of an EL6910, EJ6910 or EK1960, the previous project can be loaded to the new
device using the
Backup/Restore
mechanism.
In order to be able to use this functionality, the
Backup/Restore
mechanism must be enabled in the safety
project, and the terminals must be selected, on which the current CRC of the safety project is to be stored.
For a restore operation the user can specify the minimum number of selected terminals on which the correct
CRC must be stored.
Using the checkbox
Restore User Administration
the user can specify whether the user administration should
be transferred to the new device via the restore mechanism.
Fig. 128: Backup/Restore
In order to be able to use the
Backup/Restore
mechanism, create a backup of the current safety project and
store it on the hard disk of the controller, for sample. To carry out a restore, the user can either check when
starting the controller whether the serial number of the EL6910, EJ6910 or EK1960 has changed, or start the
restore manually via a service menu, e.g. in the visualization. Detailed information about the
Backup/Restore
mechanism is available from Beckhoff Support.
Содержание TwinSAFE EL6910
Страница 1: ...Operation Manual for EL6910 TwinSAFE Logic Terminal 1 8 0 2019 01 09 Version Date...
Страница 2: ......
Страница 62: ...Operation EL6910 62 Version 1 8 0 Fig 63 Check Safe Addresses context menu Fig 64 Check Safe Addresses dialog...
Страница 69: ...Operation EL6910 69 Version 1 8 0 Fig 73 The Safety Project Online View tab...
Страница 71: ...Operation EL6910 71 Version 1 8 0 Fig 75 Group Status Online ERROR Fig 76 Group Status Online STOP...
Страница 136: ...Appendix EL6910 136 Version 1 8 0 5 2 Certificates...
Страница 137: ...Appendix EL6910 137 Version 1 8 0...