Operation
EL6910
127
Version: 1.8.0
Fig. 178: Diagnostic object: FSLOGIC Status (F100
hex
) in the process image of the TwinSAFE component.
4.18.4
Cycle time of the safety project
The processing time of the EL6910/EJ6910 can be obtained from the CoE objects below. To determine the
cycle time, it has to be multiplied with 1.25, because this is the factor used internally for generating a delay
time before the next cycle.
4.18.4.1
Index FEA0hex: CTRL Diag Data
Index
Name
Meaning
Flags Default
FEA0:09 Actual Safety Control
Task Execution Time
Current processing time of the EL6910/EJ6910 when
logic state = 1 (RUN)
cycle time = 1.25 * value
(average value of 64 cycles)
RO
0
hex
FEA0:0A Min Safety Control Task
Execution Time
Minimum processing time of the EL6910/EJ6910
when logic state = 1 (RUN)
cycle time = 1.25 * value
RO
0
hex
FEA0:0B Actual Safety Control
Task Execution Time
Maximum processing time of the EL6910/EJ6910
when logic state = 1 (RUN)
cycle time = 1.25 * value
RO
0
hex
FEA0:15 Actual Safety Control
Task Execution Time
Current processing time of the EL6910/EJ6910 when
logic state <> 1
cycle time = 1.25 * value
(average value of 64 cycles)
RO
0
hex
FEA0:16 Min Safety Control Task
Execution Time
Minimum processing time of the EL6910/EJ6910
when logic state <> 1
cycle time = 1.25 * value
RO
0
hex
FEA0:17 Actual Safety Control
Task Execution Time
Maximum processing time of the EL6910/EJ6910
when logic state <> 1
cycle time = 1.25 * value
RO
0
hex
The minimum and maximum values can be reset by writing a value to CoE object 0x1C32:08.
4.19
Diagnosis History
The diagnostic history of the TwinSAFE devices that support this function is implemented in accordance with
the
guideline ETG.1020 Chapter 13 "Diagnosis Handling". The diagnostic messages are saved by the
TwinSAFE device in a dedicated CoE object under 0x10F3 and can be read out by the application or by
TwinCAT.
Both the control entries and the history itself can be found in the CoE object 0x10F3. The entry Newest
Message (0x10F3:02) contains the subindex of 0x10F3, which contains the latest diagnostic message, e.g.
0x06 for diagnostic message 1.
Содержание TwinSAFE EL6910
Страница 1: ...Operation Manual for EL6910 TwinSAFE Logic Terminal 1 8 0 2019 01 09 Version Date...
Страница 2: ......
Страница 62: ...Operation EL6910 62 Version 1 8 0 Fig 63 Check Safe Addresses context menu Fig 64 Check Safe Addresses dialog...
Страница 69: ...Operation EL6910 69 Version 1 8 0 Fig 73 The Safety Project Online View tab...
Страница 71: ...Operation EL6910 71 Version 1 8 0 Fig 75 Group Status Online ERROR Fig 76 Group Status Online STOP...
Страница 136: ...Appendix EL6910 136 Version 1 8 0 5 2 Certificates...
Страница 137: ...Appendix EL6910 137 Version 1 8 0...