Operation
EL6910
111
Version: 1.8.0
Fig. 151: Parameters for the PROFIsafe master connection
Parameter
Description
F_Check_Seq_Nr
Setting (0/1) to indicate whether the sequence number of the connection should be
checked.
F_Check_iPar
Setting (0/1) to indicate whether the parameterization should take place via an iPar
server.
F_SIL
Selecting the required SIL level (SIL1, SIL2, SIL3, NoSIL)
F_CRC_Length
Display of the CRC length
F_Block_ID
always 0
F_Par_Version
PROFIsafe version used (typically V2 mode)
F_Source_Add
Setting the PROFIsafe source address
F_Dest_Add
Setting the PROFIsafe destination address
F_WD_Time
Setting the watchdog time
F_iPar_CRC
i-parameter(s) for the PROFIsafe slave
F_Par_CRC
Calculated CRC across all parameters
PROFIsafe telegram only via E-bus and PROFINET/PROFIBUS
On account of the PROFIsafe policy, the use of PROFIsafe is permitted only via the PROFIBUS
and PROFINET fieldbuses or via a backplane bus, in this case for example the E-bus. The use of
PROFIsafe via other fieldbuses is impermissible for reasons connected with patent law. This must
be ensured through the use of the EL9930 segment end terminal.
The following Siemens AG patents are relevant according to the PROFIsafe profile:
- EP1267270-A2 Method for data transfer
- WO00/045562-A1 Method and device for determining the reliability of data carriers
- WO99/049373-A1 Shortened data message of an automation system
- EP1686732 Method and system for transmitting protocol data units
- EP1802019 Identification of errors in data transmission
- EP1921525-A1 Method for operation of a safety-related system
- EP13172092.2 Method and system for detection of errors
4.12.1
Valid PROFIsafe configurations
The following notes apply to PROFIsafe Master and PROFIsafe Slave configurations. PROFIsafe can be
used if a CX controller is used, which only has EtherCAT Terminals attached and only exchanges date with a
device via PROFIbus, for sample.
Содержание TwinSAFE EL6910
Страница 1: ...Operation Manual for EL6910 TwinSAFE Logic Terminal 1 8 0 2019 01 09 Version Date...
Страница 2: ......
Страница 62: ...Operation EL6910 62 Version 1 8 0 Fig 63 Check Safe Addresses context menu Fig 64 Check Safe Addresses dialog...
Страница 69: ...Operation EL6910 69 Version 1 8 0 Fig 73 The Safety Project Online View tab...
Страница 71: ...Operation EL6910 71 Version 1 8 0 Fig 75 Group Status Online ERROR Fig 76 Group Status Online STOP...
Страница 136: ...Appendix EL6910 136 Version 1 8 0 5 2 Certificates...
Страница 137: ...Appendix EL6910 137 Version 1 8 0...