Programming
TX1200
74
Version: 1.1
bActuatorCannotMove:
actuator cannot move.
bReverseFlow:
reverse flow.
bFlowSetpointNotReached:
setpoint for flow not reached.
bFlowWithClosedValve:
flow with closed valve.
bActualFlowVnom:
actual flow > nominal flow.
bFlowMeasurementError:
error during flow measurement.
bRemoteTempError:
remote temperature error.
bIntegratedTempError:
integrated temperature error.
bCommToSensorInterrupted:
communication to the sensor is interrupted.
bFreezeWarning:
freeze warning.
bGlycolDetected:
glycol detected.
bPowerSetpointNotReached:
power setpoint not reached.
6.4.2.5
St_MP_VRU_ServiceInfo
Malfunction and service information.
TYPE St_MP_VRU_ServiceInfo :
STRUCT
bError_dP_Sensor : BOOL;
bReverseAirflowDetected : BOOL;
bAirflowNotReached : BOOL;
bFlowInClosedPosition : BOOL;
bInternalActivity : BOOL;
bGearDisengaged : BOOL;
bBusWatchdogTriggered : BOOL;
bActuatorDoseNotFitToApplication : BOOL;
bPressSensorWrongConnected : BOOL;
bPressureSensorNotReached : BOOL;
bError_dP_SensorOutOfRange : BOOL;
END_STRUCT
END_TYPE
bError_dP_Sensor:
Error dp sensor.
bReverseAirflowDetected:
Reverse air flow detected.
bAirflowNotReached:
Air flow not reached.
bFlowInClosedPosition:
Flow in closed position.
bInternalActivity:
Internal activity.
bGearDisengaged:
Gear disengaged.
bBusWatchdogTriggered:
Bus watchdog triggered.
bActuatorDoseNotFitToApplication:
Actuator does not fit to application.
bPressSensorWrongConnected:
Pressure sensor connected wrong.
bPressureSensorNotReached:
Pressure sensor not reached.
bError_dP_SensorOutOfRange:
dP sensor out of range.
6.4.2.6
St_StateEV
Information on the status of the EV.