Technical data, mounting, wiring
PS1111-2403-0000
21
Version: 1.0
3.13
Environment
Environment
Operating temperature
1)
-10°C to +70°C
Reduction of the output power according to
Fig.
Output current over ambient temperature
Storage temperature
-40°C to +85°C
For storage and transport
Output load reduction
0.1A/°C
B60°C and +70°C
Load reduction due to
installation altitude
3)
0.25A/1000m or 5°C/1000m
Above 2000m, see Fig.
Output current over
installation altitude
Moisture
5 to 95% r.h.
According to IEC 60068-2-30 Do not
energize if there is condensation.
Atmospheric pressure
110-54kPa
see Fig.
Output current over installation
altitude
Installation altitude
0 to 5000m
see Fig.
Output current over installation
altitude
Overvoltage category
II
According to IEC 60664-1, for altitudes up to
5000m
Surge voltage strength
4kV (according to overvoltage
category III)
Input to PE
According to IEC 60664-1, for altitudes up to
2000m
Degree of pollution
2
According to IEC 60664-1, non-conductive
Oscillation, sinusoidal
2)
2–17.8Hz: ±1.6mm;
17.8-500Hz: 2g 2 hours/axis
According to IEC 60068-2-6
Impacts
2)
30g 6ms, 20g 11ms 3 impacts/
direction, 18 impacts in total
According to IEC 60068-2-27
1)
The working temperature is identical to the room temperature or the ambient temperature and is defined as
the air temperature 2cm below the device.
2)
Tested in conjunction with DIN rails according to EN 60715 with a height of 15mm and a thickness of
1.3mm and standard mounting position.
3)
The derating is not hardware-controlled. The user must take this into account in order to stay below the
reduced current limits, so that device overload is avoided.
Fig. 11: Output current over ambient temperature; output current over installation altitude