Technical data, mounting, wiring

PS1111-2403-0000

21

Version: 1.0

3.13

Environment

Environment

Operating temperature 

1)

-10°C to +70°C

Reduction of the output power according to
Fig. 

Output current over ambient temperature

Storage temperature

-40°C to +85°C

For storage and transport

Output load reduction

0.1A/°C

B60°C and +70°C

Load reduction due to
installation altitude 

3)

0.25A/1000m or 5°C/1000m

Above 2000m, see Fig. 

Output current over

installation altitude

Moisture

5 to 95% r.h.

According to IEC 60068-2-30 Do not
energize if there is condensation.

Atmospheric pressure

110-54kPa

see Fig. 

Output current over installation

altitude

Installation altitude

0 to 5000m

see Fig. 

Output current over installation

altitude

Overvoltage category

II

According to IEC 60664-1, for altitudes up to
5000m

Surge voltage strength

4kV (according to overvoltage
category III)

Input to PE
According to IEC 60664-1, for altitudes up to
2000m

Degree of pollution

2

According to IEC 60664-1, non-conductive

Oscillation, sinusoidal 

2)

2–17.8Hz: ±1.6mm;
17.8-500Hz: 2g 2 hours/axis

According to IEC 60068-2-6

Impacts

2)

30g 6ms, 20g 11ms 3 impacts/
direction, 18 impacts in total

According to IEC 60068-2-27

1)

 The working temperature is identical to the room temperature or the ambient temperature and is defined as

the air temperature 2cm below the device.

2)

 Tested in conjunction with DIN rails according to EN 60715 with a height of 15mm and a thickness of

1.3mm and standard mounting position.

3)

 The derating is not hardware-controlled. The user must take this into account in order to stay below the

reduced current limits, so that device overload is avoided.

Fig. 11: Output current over ambient temperature; output current over installation altitude

Содержание PS1111-2403-0000

Страница 1: ...Documentation EN PS1111 2403 0000 Power supply 24 V DC 3 8 A 1 phase 2020 10 28 Version 1 0 ...

Страница 2: ......

Страница 3: ...g diagram 16 3 8 Front side and operating elements 17 3 9 Terminals and wiring 18 3 10 Lifetime expectancy 19 3 11 MTBF 19 3 12 EMC 20 3 13 Environment 21 3 14 Protective functions and safety features 22 3 15 Dielectric strength 23 3 16 Declaration of conformity and approvals 24 3 17 Dimensions and weight 25 4 Application notes 26 4 1 Charging batteries 26 4 2 Series connection 26 4 3 Parallel use...

Страница 4: ...Table of contents PS1111 2403 0000 4 Version 1 0 ...

Страница 5: ... requirements are met The power supply is part of the PS1000 family and has a width of 36 mm A DC OK LED monitors the status of the output voltage Overview of technical data Overview of technical data PS1111 2403 0000 Output voltage DC 24V nominal factory setting 24 1V Adjustment range 24 28V Output current 3 8 3 2A below 60 C 2 8 2 4A at 70 C Linear load reduction between 60 C and 70 C Input volt...

Страница 6: ...r are registered trademarks of and licensed by Beckhoff Automation GmbH Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owners Patent Pending The EtherCAT Technology is covered including but not limited to the following patent applications and patents EP1590927 EP1789857 EP1456722 EP2137893 DE1020151057...

Страница 7: ...s device is designed for installation in a housing and is intended for general professional use for example in industrial control systems or office communication and measuring equipment Do not use this power supply in installations where a malfunction could cause serious injury or danger to human life Exclusion of liability All the components are supplied in particular hardware and software config...

Страница 8: ...lution 2 in controlled environments No con densation or frost is allowed The device housing offers IP20 protection The housing offers no protection against spilled liq uids The device insulation is designed to withstand pulse voltages of overvoltage category III accord ing to IEC 60664 1 The device is designed to meet the requirements of protection class I according to IEC 61140 It must not be use...

Страница 9: ...with tolerances e g AC 230 V 10 The calculated total range then indicates the working range of the device Example DC 12 V refers to a 12 V battery regardless of whether it is fully charged 13 7 Vdc or discharged 10 Vdc 230 Vac A value followed by the unit Vac or Vdc is an instantaneous value that does not contain any additional tolerances 50 Hz vs 60 Hz Unless otherwise specified AC 100 V and AC 2...

Страница 10: ...ety and installation requirements 8 AC input AC100V AC120V AC230V Input current Typ 1 69A 1 45A 0 95A At 24V 3 8A see Fig Input current over output current Power factor Typ 0 6 0 58 0 45 At 24V 3 8A see Fig Power factor over output current Start up delay Typ 50ms 50ms 50ms See Fig Switch on behavior definitions Rise time Typ 21ms 21ms 20ms At 24V 3 8A constant current load 0mF load capaci tance se...

Страница 11: ...Technical data mounting wiring PS1111 2403 0000 11 Version 1 0 3 2 DC input Do not operate this power supply with DC input voltage ...

Страница 12: ... suppression capacitors during the first few microseconds after switching on is not taken into account AC 100V AC 120V AC 230V Input inrush current Typ 14Apeak 18Apeak 40Apeak At 40 C cold start Typ 12Apeak 16Apeak 35Apeak At 25 C cold start Max 17Apeak 22Apeak 48Apeak At 40 C cold start Max 15Apeak 20Apeak 43Apeak At 25 C cold start Inrush energy Max 0 3A2 s 0 4A2 s 1 7A2 s At 40 C cold start Fig...

Страница 13: ...lue see Fig Output voltage over output current typ Residual ripple and ripple voltage Max 100mVss Bandwidth 20 Hz to 20 MHz 50 Ohm Output current Nom 3 8A At 24 V and ambient temperature below 60 C Nom 3 2A At 24V V and 70 C ambient temperature Nom 2 8A At 28 V and ambient temperature below 60 C Nom 2 4A At 28 V and 70 C ambient temperature Overload protection Yes Electronic protection against ope...

Страница 14: ... of input power The hold up time depends on the output load At no load the hold up time can be up to several seconds During this time the green DC OK lamp also lights up AC 100V AC 120V AC 230V Hold up time Typ 14ms 25ms 119ms At 24V 3 8A Typ 40ms 60ms 242ms At 24V 1 9A Min 11 5ms 20ms 95ms At 24V 3 8A Min 32ms 48ms 194ms At 24V 1 9A Fig 6 Hold up time over input voltage switch off behavior defini...

Страница 15: ...W 4 3W 3 8W At 24V 1 9A half load Typ 9 5W 7 9W 6 0W At 24V 3 8A full load The average efficiency is based on assumptions for a typical application with the power supply unit operating at 25 of the nominal load during 25 of the time 50 of the nominal load during 25 of the time 75 of the nominal load during 25 of the time and 100 of the nominal load during the remaining time Fig 7 Efficiency over o...

Страница 16: ...Technical data mounting wiring PS1111 2403 0000 16 Version 1 0 3 7 Functional wiring diagram Fig 9 Functional wiring diagram ...

Страница 17: ...ains input N L Mains input L Protective conductor PE Output terminals screw terminals Designation B Description two identical positive poles positive output two identical negative poles negative output Potentiometer for the output voltage Designation C Description Potentiometer Factory setting 24 1 V DC OK LED Designation D Description LED green Lights up when the output voltage is above 18V ...

Страница 18: ...to be finger safe according to IP20 and are suitable for field or factory wiring Technical data All connections Connection cross section e max 6mm f max 4mm a max 4mm d 2 8mm Connection cross section AWG e AWG 20 10 f AWG 20 10 a AWG 20 10 d 2 8mm Strip length 7mm 0 28inch e solid wire f stranded wire a with ferrule ...

Страница 19: ...hich is calculated from the statistical failure rate of the components and indicates the reliability of a device It is a statistical representation of the probability of equipment failure and does not necessarily represent the service life of a product The MTBF number is a statistical representation of the probability of equipment failure An MTBF number of 1 000 000h for example means that statist...

Страница 20: ...f less than 20ms Without additional measures to reduce conducted emissions at the output e g by using a filter the device is not suitable for supplying a local DC power network in residential commercial or small business environments There are no restrictions for local DC power networks in industrial environments EMC interference immunity Strong transients VDE 0160 Over the entire load range 750V ...

Страница 21: ...C 60664 1 for altitudes up to 5000m Surge voltage strength 4kV according to overvoltage category III Input to PE According to IEC 60664 1 for altitudes up to 2000m Degree of pollution 2 According to IEC 60664 1 non conductive Oscillation sinusoidal 2 2 17 8Hz 1 6mm 17 8 500Hz 2g 2 hours axis According to IEC 60068 2 6 Impacts2 30g 6ms 20g 11ms 3 impacts direction 18 impacts in total According to I...

Страница 22: ...aximum output voltage to 32V The output switches off To at tempt a restart turn off the input voltage for at least 90 seconds Protection class I According to EN IEC 61140 Protection class IP 20 According to EN IEC 60529 Overtemperature protection Protection against input transients MOV metal oxide varistor For further information see EMC chapter 20 Input fuse included Non replaceable slow blow fus...

Страница 23: ... 2s rising and 2s falling Connect all input terminals and all output poles to each other before performing the tests During the test set the cut off current to the value shown in the table below Fig 12 Dielectric strength A B C Type test 60s 2500Vac 3000Vac 1000Vac Component test 5s 2500Vac 2500Vac 500Vac Field test 5s 2000Vac 2000Vac 500Vac Setting the cut off current 2mA 2mA 6mA We recommend con...

Страница 24: ...ata mounting wiring PS1111 2403 0000 24 Version 1 0 3 16 Declaration of conformity and approvals EU declaration of conformity UL Certificate UL 61010 1 2 201 Applicable for US and Canada UL Certificate NEC CLASS 2 ...

Страница 25: ...al installation depth required DIN rail Use 35 mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm Weight 270g Housing material High quality polycarbonate ABS blend material Installation clearances See chapter on Safety instructions and installation requirements 8 Ingress protection Small parts such as screws nuts etc with a diameter of more than 4 2 mm Fig 13 Front side vi...

Страница 26: ...Operation on two phases Make sure that the conductor connected to the N terminal is fused appropriately 4 5 Use in a tightly sealed enclosure When the power supply is installed in a tightly sealed enclosure the temperature inside the housing is higher than outside In this case the temperature inside the housing is considered the ambient temperature for the power supply The power supply is position...

Страница 27: ...using protection class IP66 PK 9516 100 plastic 110x180x165mm Rittal housing protection class IP66 PK 9516 100 plastic Input voltage 230Vac 230Vac Load 24V 3 04A 80 24V 3 8A 100 Temperature inside the housing 30 3 C 31 7 C Temperature outside the housing 21 0 C 21 0 C Temperature increase 9 3K 10 7 K ...

Страница 28: ...Appendix PS1111 2403 0000 28 Version 1 0 5 Appendix 5 1 Documentation issue status Version Comment 1 0 First public issue 0 2 Addenda corrections 0 1 Preliminary documentation for PS1111 2403 0000 ...

Страница 29: ...ckhoff components there Beckhoff Support Support offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with other wide ranging services support design programming and commissioning of complex automation systems and extensive training program for Beckhoff system components Hotline 49 5246 963 157 Fax 49 5246 963 9157 e mail ...

Страница 30: ......

Страница 31: ...Beckhoff Automation GmbH Co KG Hülshorstweg 20 33415 Verl Germany Phone 49 5246 9630 info beckhoff com www beckhoff com More Information www beckhoff com ps1111 2403 0000 ...

Отзывы: