Technical data, mounting, wiring
PS1061-2405-0000
17
Version: 1.0
3.6
DC-OK relay contact
This function monitors the output voltage generated by the power supply itself.
The contact closes
when the output voltage reaches 22 V.
The contact opens
as soon as the output voltage falls below 22 V.
Switching hysteresis
typ. 0.7 V
Contact load capacity
Maximum 60 Vdc 0.3 A, 30 Vdc 1 A, 30 Vac 0.5 A, ohmic load
Minimum permissible load: 1 mA at 5 Vdc
Insulation voltage
Fig. 6: Behavior of the DC-OK relay contact
Содержание PS1061-2405-0000
Страница 1: ...Documentation EN PS1061 2405 0000 Power supply 24 V DC 5 A 1 phase AC 200 240 V 2021 06 16 Version 1 0...
Страница 2: ......
Страница 4: ...Table of contents PS1061 2405 0000 4 Version 1 0...
Страница 35: ......