Technical data, mounting, wiring
PS1061-2405-0000
16
Version: 1.0
3.5
Hold-up time
The hold-up time is the time during which the output voltage of a power supply unit remains within the
specification after a loss of input power. The hold-up time depends on the output load. Without load the hold-
up time can be several seconds. The green DC-OK lamp also lights up during this time.
230 Vac
Mains failure
Hold-up time
Typ.
69 ms
At 24 V, 2.5 A, see Fig.
Hold-up time over input voltage
Min.
61 ms
At 24 V, 2.5 A, see Fig.
Hold-up time over input voltage
Typ.
33 ms
At 24 V, 5 A, see Fig.
Hold-up time over input voltage
Min.
29 ms
At 24 V, 5 A, see Fig.
Hold-up time over input voltage
Fig. 5: Hold-up time over input voltage; switch-off behavior, definitions