Technical data, mounting, wiring
PS1011-2420-0000
13
Version: 1.0
3.4
Output
The output provides an SELV/PELV nominal voltage that is electrically isolated from the input voltage.
The output is designed to supply any type of load, including capacitive and inductive loads. If very large
capacitors, such as EDLCs (electrical double-layer capacitors or "UltraCaps") with a capacitance > 3F are
connected to the output, the device can charge the capacitor intermittently.
The output is electronically protected against overload, no-load and short circuit. In the event of a protection
event, audible noises may occur.
Output voltage
Nom.
24V
Adjustment range
Min.
24-28V
Guaranteed value
Max.
30V
This is the maximum output voltage that can occur in the end position of the potentiome-
ter in clockwise direction due to tolerances. It is not a guaranteed value that can be
achieved.
Factory settings
typ.
24.1V
±0.2%, at full load (cold device)
Line regulation
Max.
10mV
Between 90 and 300Vac
Load regulation
Max.
100mV
Between 0 and 20A, static value, see Fig.
Output voltage over output current, typ.
Residual ripple and
ripple voltage
Max.
100mV
ss
Bandwidth 20 Hz to 20 MHz, 50 Ohm
Output current
1)
Nom.
20A
At 24V and an ambient temperature below 55°C, see Fig.
Output current over ambient
temperature
Nom.
12.5A
At 24V and 70°C ambient temperature, see Fig.
Output voltage over output current, typ.
Nom.
17.1A
At 28V and an ambient temperature below 55°C, see Fig.
Output current over ambient
temperature
Nom.
10.7A
At 28V and 70°C ambient temperature, see Fig.
Output voltage over output current, typ.
Overload characteris-
tics
Continuous
current
Output voltage > 13Vdc, see Fig.
Output voltage over output current, typ.
Hiccup mode
2)
Output voltage < 13Vdc, see Fig.
Output voltage over output current, typ.
Overload/short circuit
current
Max.
27.5A
Continuous current, see Fig.
Short-circuit at output, typ.
typ.
30A
Intermittent current peak value for typ. 1s
Load impedance 50mOhm, see Fig.
Short circuit at the output
The discharge current of the output capacitors is not included
Max.
11A
intermittent mean current value (rms.)
Load impedance 50mOhm, see Fig.
Short circuit at the output
Output capacity
typ.
6,800μF
Included in the power supply
Load feedback
Max.
35V
The device is robust and will not indicate a malfunction if a load voltage is fed back into
the power supply. It does not matter whether the power supply is switched on or off. The
absorbed energy can be calculated by means of the built-in large-size output capacitor.
1)
Linear derating b55°C and +70°
2)
In case of severe overload (when the output voltage drops below 13V) the power supply delivers a continuous output current for
2-5 seconds. The output is then switched off for approx. 7 second before a new start attempt is automatically made for 1 second. This
cycle is repeated as long as the overload exists. The device starts operating normally again once the overload has been rectified.