Technical data, mounting, wiring
PS1011-2420-0000
10
Version: 1.0
3
Technical data, mounting, wiring
3.1
AC input
AC input
AC input
Nom.
AC 100-240V
Suitable for TN, TT and IT networks with alternating voltage
AC input range
Min.
90-264Vac
Continuous operation
Min.
264-300Vac
For up to 500 ms max.
Permissible voltage L or N to
earth
Max.
300Vac
Continuous according to IEC 60664-1
Input frequency
Nom.
50-60Hz
±6%
Turn-on voltage
typ.
81Vac
Static, see Fig.
Input voltage range
,
Shut-down voltage
typ.
63Vac/71Vac
At zero load / nominal load, static value, see Fig.
Input voltage
range,
External input protection
See recommendations in chapter
Safety instructions and installation requirements [
AC input
AC100V
AC120V
AC230V
Input current
typ.
5.2A
4.3A
2.3A
At 24V, 20A, see Fig.
Input current over output current
Power factor
1)
typ.
0.99
0.99
0.97
At 24V, 20A, see Fig.
Power factor over output current
Crest factor
2)
typ.
1.6
1.7
2.0
At 24V, 20A
Start-up delay
typ.
420ms
300ms
230ms
See Fig.
Switch-on behavior definitions
Rise time
typ.
100ms
100ms
100ms
At 24V, 20A constant current load, 0mF load capacity,
see Fig.
Switch-on behavior definitions
typ.
140ms
140ms
140ms
At 24V, 20A constant current load, 20mF load capac-
ity, see Fig.
Switch-on behavior definitions
Turn-on overshoot
Max.
200 mV
200 mV
200 mV
See Fig.
Switch-on behavior definitions
1)
The power factor is the ratio of real (or active) power to apparent power in an AC circuit.
2)
The crest factor is the mathematical ratio of the peak value over the RMS value of the input current waveform.
Fig. 1: Input voltage range; switch-on behavior definitions
Fig. 2: Input current over output current; power factor over output current
Содержание PS1011-2420-0000
Страница 1: ...Documentation EN PS1011 2420 0000 Power supply 24 V DC 20 A 1 phase 2020 10 27 Version 1 0 ...
Страница 2: ......
Страница 4: ...Table of contents PS1011 2420 0000 4 Version 1 0 ...
Страница 31: ......