Documentation | EN

PS1011-2410-0000

Power supply 24 V DC, 10 A, 1-phase

2020-10-27 | Version: 1.0

Содержание PS1011-2410-0000

Страница 1: ...Documentation EN PS1011 2410 0000 Power supply 24 V DC 10 A 1 phase 2020 10 27 Version 1 0...

Страница 2: ......

Страница 3: ...unctional wiring diagram 19 3 11 Front side and operating elements 20 3 12 EMC 21 3 13 Environment 22 3 14 Protective functions and safety features 23 3 15 Dielectric strength 24 3 16 Declaration of c...

Страница 4: ...Table of contents PS1011 2410 0000 4 Version 1 0...

Страница 5: ...is part of the PS1000 family and has a width of 49 mm A DC OK LED and a potential free relay contact monitor the status of the output voltage Overview of technical data Overview of technical data PS1...

Страница 6: ...are registered trademarks of and licensed by Beckhoff Automation GmbH Other designations used in this publication may be trademarks whose use by third parties for their own purposes could violate the...

Страница 7: ...ith tolerances e g AC 230 V 10 The calculated total range then indicates the working range of the device Example DC 12 V refers to a 12 V battery regardless of whether it is fully charged 13 7 Vdc or...

Страница 8: ...device is designed for installation in a housing and is intended for general professional use for example in industrial control systems or office communication and measuring equipment Do not use this...

Страница 9: ...the device when it is switched on or immediately after it has been switched off Hot sur faces can cause burns Further notes on installation requirements This device contains no parts that require main...

Страница 10: ...1 18A At 24V 10A see Fig Input current over output current Power factor 1 typ 0 99 0 98 0 93 At 24V 10A see Fig Power factor over output current Crest factor 2 typ 1 6 1 7 2 0 At 24V 10A Start up dela...

Страница 11: ...Technical data mounting wiring PS1011 2410 0000 11 Version 1 0 3 2 DC input Do not operate this power supply with DC input voltage...

Страница 12: ...nput inrush current Max 14 5Apeak 17Apeak 32Apeak At 40 C cold start typ 7Apeak 8 5Apeak 16Apeak At 25 C cold start typ 11 5Apeak 14Apeak 26Apeak At 40 C cold start Inrush energy Max 0 2A s 0 3A s 1A...

Страница 13: ...ee Fig Output voltage over output current typ Hiccup mode1 Output voltage 13Vdc see Fig Output voltage over output current typ Short circuit current Min 11A Load impedance 50mOhm see Fig Output voltag...

Страница 14: ...5ms At 24V 5A see Fig Hold up time over input voltage Min 53ms 53ms 53ms At 24V 5A see Fig Hold up time over input voltage typ 32ms 32ms 32ms At 24V 10A see Fig Hold up time over input voltage Min 26m...

Страница 15: ...ld voltage typ 21 8V fixed The contact closes When the output voltage reaches 21 8V The contact opens When the output voltage falls below 21 7V Contact load capacity Maximum 60Vdc 0 3A 30Vdc 1A 30Vac...

Страница 16: ...5W 7 5W At 24V 5A half load typ 17 5W 15 3W 12 1W At 24V 10A full load The average efficiency is based on assumptions for a typical application with the power supply unit operating at 25 of the nomina...

Страница 17: ...MTBF stands for Mean Time Between Failure which is calculated from the statistical failure rate of the components and indicates the reliability of a device It is a statistical representation of the pr...

Страница 18: ...G 20 10 d 2 8mm e AWG 20 10 f AWG 20 10 a AWG 20 10 d 2 8mm e AWG 28 16 f AWG 28 16 a AWG 28 16 d 1 6 mm Strip length 7mm 0 28inch 7mm 0 28inch 7mm 0 28inch e solid wire f stranded wire a with ferrule...

Страница 19: ...Technical data mounting wiring PS1011 2410 0000 19 Version 1 0 3 10 Functional wiring diagram Fig 9 Functional wiring diagram...

Страница 20: ...als Designation B Description two identical positive poles positive output two identical negative poles negative output Potentiometer for the output voltage Designation C Description Potentiometer Gua...

Страница 21: ...SPR 16 2 1 Limit values for the DC power connection according to EN 61000 6 3 not met Interference emission EN 55011 EN 55022 Class B Harmonic input current EN 61000 3 2 Met class A limits Voltage flu...

Страница 22: ...ion altitude IEC 62477 1 overvoltage category II Load reduction due to installation altitude 15W 1000m or 5 C 1000m Above 2000m see Fig Output current over installation altitude Overvoltage category I...

Страница 23: ...107 1 01 Overtemperature protection yes Output shutdown with automatic restart Protection against input transients MOV metal oxide varistor For further information see EMC chapter 21 Input fuse yes F...

Страница 24: ...uirements according to EN60204 1 section 6 4 1 we recommend that either the positive pole the negative pole or any other part of the output circuit is connected to the protective earthing system This...

Страница 25: ...Technical data mounting wiring PS1011 2410 0000 25 Version 1 0 3 16 Declaration of conformity and approvals EU declaration of conformity UL Certificate UL 61010 1 2 201 Applicable for US and Canada...

Страница 26: ...calculate the total installation depth required DIN rail Use 35 mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm Weight 540g Plastic material of the housing Flame retardant...

Страница 27: ...circuits The additional current peak current is supplied by the power converter and the built in large size output capacitors of the power supply The capacitors are discharged during such an event whi...

Страница 28: ...long as the sum of the output voltages does not exceed 150Vdc Voltages with a potential above 60Vdc are no longer defined as safety extra low voltage SELV and can be dangerous Such voltages must be p...

Страница 29: ...nsidered the ambient temperature for the power supply The power supply is positioned at the center of the housing There are no other heat generating elements in the housing The temperature sensor in t...

Страница 30: ...Appendix PS1011 2410 0000 30 Version 1 0 5 Appendix 5 1 Documentation issue status Version Comment 1 0 First public issue Addenda corrections 0 1 Preliminary documentation for PS1011 2410 0000...

Страница 31: ...khoff components there Beckhoff Support Support offers you comprehensive technical assistance helping you not only with the application of individual Beckhoff products but also with other wide ranging...

Страница 32: ......

Страница 33: ...Beckhoff Automation GmbH Co KG H lshorstweg 20 33415 Verl Germany Phone 49 5246 9630 info beckhoff com www beckhoff com More Information www becklhoff com ps1011 2410 0000...