Beckhoff KM2042 Скачать руководство пользователя страница 1

Documentation

KM2042

Sixteen channel digital output module with D-Sub Connector

2.0.0
2017-11-20

Version:
Date:

Содержание KM2042

Страница 1: ...Documentation KM2042 Sixteen channel digital output module with D Sub Connector 2 0 0 2017 11 20 Version Date...

Страница 2: ......

Страница 3: ...fety instructions 6 1 3 Documentation Issue Status 7 2 Product overview 8 2 1 Introduction 8 2 2 Technical Data 9 3 Mounting and wiring 10 3 1 Recommended mounting rails 10 3 2 Mounting and demounting...

Страница 4: ...Table of contents KM2042 4 Version 2 0 0...

Страница 5: ...e data diagrams and descriptions in this documentation Trademarks Beckhoff TwinCAT EtherCAT Safety over EtherCAT TwinSAFE XFC and XTS are registered trademarks of and licensed by Beckhoff Automation G...

Страница 6: ...iliar with the applicable national standards Description of symbols In this documentation the following symbols are used with an accompanying safety instruction or note The safety instructions must be...

Страница 7: ...he firmware and hardware versions delivery state can be taken from the serial number printed on the side of the terminal module Syntax of the serial number Structure of the serial number WW YY FF HH W...

Страница 8: ...The KM2042 Terminal Module combines 16 digital outputs in a Sub D plug connector in a compact design The binary control signals are transferred electrically isolated to the actuators at the process le...

Страница 9: ...s Terminals or 80 cm one KM2042 corresponds to 2 standard Bus Terminals here Data width in the input process image 0 bit Data width in the output process image 16 bit Dimensions without antenna W x H...

Страница 10: ...ding to EN 60715 3 2 Mounting and demounting terminals with front unlocking The terminal modules are fastened to the assembly surface with the aid of a 35 mm mounting rail e g mounting rail TH 35 15 N...

Страница 11: ...the cables Demounting Remove all the cables Lever the unlatching hook back with thumb and forefinger 3 An internal mechanism pulls the two latching lugs 3a from the top hat rail back into the terminal...

Страница 12: ...Mounting and wiring KM2042 12 Version 2 0 0 3 3 Dimensions Fig 2 KM2042 Dimensions...

Страница 13: ...16 outputs deliver load currents of up to 0 5 A although the total current from all the outputs must not exceed 4 A The signal connection is made through a 25 pin D Sub socket The outputs are short ci...

Страница 14: ...components there Beckhoff Headquarters Beckhoff Automation GmbH Co KG Huelshorstweg 20 33415 Verl Germany Phone 49 0 5246 963 0 Fax 49 0 5246 963 198 e mail info beckhoff com Beckhoff Support Support...

Страница 15: ...List of illustrations KM2042 15 Version 2 0 0 List of illustrations Fig 1 KM2042 8 Fig 2 KM2042 Dimensions 12 Fig 3 Assignment of the 25 pin D sub socket 13 Fig 4 Block diagram 13...