Product overview
KL4132
10
Version: 3.0
2.3
Basic function principles
The KL4132 analog output terminal generates signals in the range from -10 V to +10 V. The terminal
supplies the output voltage with a resolution of up to 16 bits. The output voltage is output electrically isolated
from the terminal bus level.
The LEDs indicate the operating state of the associated terminal channels.
• green Run LED:
◦ On: Normal operation
◦ Off: Watchdog timer overflow has occurred. If no process data are transmitted by the Bus
Coupler for 100 ms, the green LEDs go out. The output assumes a user-specified voltage (see
Process data input format
In the delivery state the process data are shown in two's complement form (integer -1 corresponds to
0xFFFF).
Output value
Process data
dec
hex
-10 V
-32767
0x8001
-5 V
-16383
0xC001
0 V
0
0x0000
5 V
16383
0x3FFF
10 V
32767
0x7FFF
Process data
The process data arriving from the Bus Coupler are output to the process:
Y_0 = B_a + A_a*X
Y_dac = Y_0
(1.0)
Neither user nor manufacturer scaling is active.
Y_1 = B_h + A_h * X
Y_dac = Y_1
(1.1)
Manufacturer scaling active
Y_2 = B_w + A_w * X
Y_dac = Y_2
(1.2)
User scaling active
Y_1 = B_h + A_h * X
Y_dac = B_w + A_w * Y_1
(1.3)
(1.4)
Manufacturer and user scaling active
Key
Name
Name
Register
X
PLC process data
-
B_a
Hardware compensation offset
A_a
Hardware compensation gain
B_h
Manufacturer scaling: Offset
A_h
Manufacturer scaling: Gain
B_w
User scaling: Offset
A_w
User scaling: Gain
Y_dac
Output value for the D/A converter
-
The equations of the straight line are enabled via register
Содержание KL4132
Страница 2: ......
Страница 4: ...Table of contents KL4132 4 Version 3 0...