Product overview
2.3
KL2535 - LED displays
LED indicators
Fig. 2: KL2535 - LEDs
LED
Display
Run (green)
reserved
Data transmission on the K-bus is active
Enable A (green) off
Channel 1 is either not enabled or not ready to operate.
on
Channel 1 is enabled and is ready to operate.
-
reserved
Error A (red)
on
There is an error at channel 1
Power (green)
off
The power supply voltage is absent (less than 7 V).
on
The power supply voltage is present (more than 8 V).
Enable B (green) off
Channel 2 is either not enabled or not ready to operate.
on
Channel 2 is enabled and is ready to operate.
Warning (yellow) on
The internal temperature has risen to more than 80°C, or the power supply
voltage has dropped.
Error B (red)
on
There is an error at channel 2