Mounting and wiring
KL1501, KL1512
19
Version: 3.1.0
3.4
KL1501, KL1512 - Connection
Fig. 11: KL1502, KL1512 - Connection
KL1501
Terminal point
Description
Name
No.
Up/down CLOCK1
gate
1
Up/down counter input (operation mode: up/down counter)
Input gate (operation mode: counter with gate function)
CLOCK1 input (operation mode: 2 counters)
+24 V
2
+24 V (internally connected to terminal point 6 and positive power contact)
0 V
3
0 V (internally connected to terminal point 7 and negative power contact)
Output 1
4
Output 1
Clock
5
Clock input
+24 V
6
+24 V (internally connected to terminal point 2 and positive power contact)
0 V
7
0 V (internally connected to terminal point 3 and negative power contact)
Output 2
8
Output 2
KL1512
Terminal point
Description
Name
No.
Input 1
1
Input 1
+24 V
2
+24 V (internally connected to terminal point 6 and positive power contact)
0 V
3
0 V (internally connected to terminal point 7 and negative power contact)
n.c.
4
Not connected
Input 2
5
Input 2
+24 V
6
+24 V (internally connected to terminal point 2 and positive power contact)
0 V
7
0 V (internally connected to terminal point 3 and negative power contact)
n.c.
8
Not connected