Mounting and wiring
KL1xxx
35
Version: 1.0.0
3.2
Installation instructions for enhanced mechanical load
capacity
WARNING
Risk of injury through electric shock and damage to the device!
Bring the Bus Terminal system into a safe, de-energized state before starting mounting, disassembly or
wiring of the Bus Terminals!
Additional checks
The terminals have undergone the following additional tests:
Verification Explanation
Vibration
10 frequency runs in 3 axes
6 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude
60.1 Hz < f < 500 Hz acceleration 5
g
, constant amplitude
Shocks
1000 shocks in each direction, in 3 axes
25
g
, 6 ms
Additional installation instructions
For terminals with enhanced mechanical load capacity, the following additional installation instructions apply:
• The enhanced mechanical load capacity is valid for all permissible installation positions
• Use a mounting rail according to EN 60715 TH35-15
• Fix the terminal segment on both sides of the mounting rail with a mechanical fixture, e.g. an earth
terminal or reinforced end clamp
• The maximum total extension of the terminal segment (without coupler) is:
64 terminals (12 mm mounting with) or 32 terminals (24 mm mounting with)
• Avoid deformation, twisting, crushing and bending of the mounting rail during edging and installation of
the rail
• The mounting points of the mounting rail must be set at 5 cm intervals
• Use countersunk head screws to fasten the mounting rail
• The free length between the strain relief and the wire connection should be kept as short as possible. A
distance of approx. 10 cm should be maintained to the cable duct.
3.3
Connection
3.3.1
Connection system
WARNING
Risk of electric shock and damage of device!
Bring the bus terminal system into a safe, powered down state before starting installation, disassembly or
wiring of the bus terminals!
Overview
The Bus Terminal system offers different connection options for optimum adaptation to the respective
application:
• The terminals of ELxxxx and KLxxxx series with standard wiring include electronics and connection
level in a single enclosure.
Содержание KL1 Series
Страница 1: ...Documentation KL1xxx Digital input terminals 24 V DC 1 0 0 2020 05 08 Version Date...
Страница 2: ......
Страница 9: ...Product overview KL1xxx 9 Version 1 0 0 2 2 KL1002 KL1012 Introduction Fig 1 KL1002 Fig 2 KL1012...
Страница 13: ...Product overview KL1xxx 13 Version 1 0 0 2 3 KL1104 KL1114 Introduction Fig 5 KL1104 Fig 6 KL1114...
Страница 16: ...Product overview KL1xxx 16 Version 1 0 0 2 4 KL1402 KL1412 Introduction Fig 8 KL1402 Fig 9 KL1412...
Страница 19: ...Product overview KL1xxx 19 Version 1 0 0 2 5 KL1404 KL1414 KL1434 Introduction Fig 11 KL1404 Fig 12 KL1414...
Страница 25: ...Product overview KL1xxx 25 Version 1 0 0 Fig 18 KL1488 Fig 19 KL1498...
Страница 29: ...Product overview KL1xxx 29 Version 1 0 0 2 7 KL1862 KL1862 0010 KL1872 Introduction Fig 22 KL1862 Fig 23 KL1872...