Commissioning/configuration of IO-Link master/device
EPI3xxx, ERI3xxx
48
Version: 1.2
5.1.4
Restoring the delivery state of an EtherCAT device
To restore the delivery state for backup objects of the EP6224-xxxx (IO-Link Master), the CoE object
“Restore default parameters”, “Subindex 001” can be selected in the TwinCAT System Manager (Config
mode) (see following figure).
Fig. 49: Selecting the Restore default parameters PDO
Double-click on “SubIndex 001” to enter the “Set Value dialog” (see following figure). Enter the value
1684107116
in field “Dec” or the value
0x64616F6C
in field “Hex” and confirm with OK.
All backup objects are reset to the delivery state.
Fig. 50: Entering a restore value in the Set Value Dialog
5.2
Accessing IO-Link parameters
The exchange of the acyclic data takes place via a specified index and subindex range that is device-specific
and can be read about in the corresponding vendor documentation.