Commissioning/configuration of IO-Link master/device
EPI3xxx, ERI3xxx
41
Version: 1.2
Fig. 43: Process Data tab
Sync Manager
Lists the configuration of the Sync Manager (SM).
If the IO-Link master has a mailbox, SM0 is used for the mailbox output (MbxOut) and SM1 for the mailbox
input (MbxIn).
SM2 is used for the output process data (outputs) and SM3 (inputs) for the input process data.
If an input is selected, the corresponding PDO assignment is displayed in the
PDO Assignment
list below.
PDO Assignment
PDO assignment of the selected Sync Manager. All PDOs defined for this Sync Manager type are listed
here:
• If the output Sync Manager (outputs) is selected in the Sync Manager list, all RxPDOs are displayed.
• If the input Sync Manager (inputs) is selected in the Sync Manager list, all TxPDOs are displayed.
The selected entries are the PDOs involved in the process data transfer. In the tree diagram of the System
Manager these PDOs are displayed as variables of the IO-Link master. The name of the variable is identical
to the
Name
parameter of the PDO, as displayed in the PDO list. If an entry in the PDO assignment list is
deactivated (not selected and greyed out), this indicates that the input is excluded from the PDO assignment.
In order to be able to select a greyed out PDO, the currently selected PDO has to be deselected first.
Activation of PDO assignment
• the IO-Link master has to run through the PS status transition cycle (from pre-operational to
safe-operational) once (see
),
• and the System Manager has to reload the IO-Link master (
button)