Commissioning/Configuration
EP6002-0002
56
Version: 1.0
Index A010 COM Diag data Ch.2
Index (hex) Name
Meaning
Data type
Flags Default
A010:0
COM Diag data
Ch.2
UINT8
RO
0x21 (33
dec
)
A010:01
Buffer overflow
A buffer overflow has occurred.
BOOLEAN
RO
0x00 (0
dec
)
A010:02
Parity error
A parity error has occurred.
BOOLEAN
RO
0x00 (0
dec
)
A010:03
Framing error
A framing error has occurred.
BOOLEAN
RO
0x00 (0
dec
)
A010:04
Overrun error
An overrun error has occurred.
BOOLEAN
RO
0x00 (0
dec
)
A010:05
Buffer full
The receive FIFO is full.
BOOLEAN
RO
0x00 (0
dec
)
A010:11
Data bytes in send
buffer
Number of data bytes in the send FIFO
UINT16
RO
0x0000 (0
dec
)
A010:21
Data bytes in re-
ceive buffer
Number of data bytes in the receive FIFO
UINT16
RO
0x0000 (0
dec
)
Index F000 Modular device profile
Index (hex) Name
Meaning
Data type
Flags Default
F000:0
Modular device pro-
file
General information for the modular device profile
UINT8
RO
0x02 (2
dec
)
F000:01
Module index dis-
tance
Index distance of the objects of the individual channels
UINT16
RO
0x0010 (16
dec
)
F000:02
Maximum number of
modules
Number of channels
UINT16
RO
0x0002 (2
dec
)
Index F008 Code word
Index (hex) Name
Meaning
Data type
Flags Default
F008:0
Code word
UINT32
RW
0x00000000 (0
dec
)
Index F010 Module list
Index (hex) Name
Meaning
Data type
Flags Default
F010:0
Module list
UINT8
RW
0x02 (2
dec
)
F010:01
SubIndex 001
UINT32
RW
0x00000258
(600
dec
)
F010:02
SubIndex 002
UINT32
RW
0x00000258
(600
dec
)