![Beckhoff EP3204 Скачать руководство пользователя страница 76](http://html1.mh-extra.com/html/beckhoff/ep3204/ep3204_documentation_2719256076.webp)
Commissioning/Configuration
EP3204 and EP3314
76
Version: 2.2
Index 8030: TC Settings Ch.4
Index (hex) Name
Meaning
Data type
Flags
Default
8030:19
Sensor type
Thermocouple
UINT16
RW
0x0000 (0
dec
)
0
Type K -200 °C to 1370 °C
1
Type J -100°C to 1200°C
2
Type L 0°C to 900°C
3
Type E -100°C to 1000°C
4
Type T -200°C to 400°C
5
Type N -100°C to 1300°C
6
Type U 0°C to 600°C
7
Type B 600°C to 1800°C
8
Type R 0°C to 1767°C
9
Type S 0°C to 1760°C
10
Type C 0°C to 2320°C
100 ± 30 mV (1 µV resolution)
101 ± 60 mV (2 µV resolution)
102 ± 75 mV (4 µV resolution)
8030:1B
Wire calibration
1/32 ohm
Only for 2-wire measurements:
contains the resistance of the supply line for the tempera-
ture sensor (in 1/32 ohm).
INT16
RW
0x0000 (0
dec
)
6.6.2
Objects for regular operation
The EP3314 has no such objects.
6.6.3
Standard objects (0x1000-0x1FFF)
The standard objects have the same meaning for all EtherCAT slaves.
Index 1000: Device type
Index (hex) Name
Meaning
Data type
Flags
Default
1000:0
Device type
Device type of the EtherCAT slave: The Low-Word con-
tains the CoE profile used (5001). The High-Word con-
tains the module profile according to the modular device
profile.
UINT32
RO
0x014A1389
(21631881
dec
)
Index 1008: Device name
Index (hex) Name
Meaning
Data type
Flags
Default
1008:0
Device name
Device name of the EtherCAT slave
STRING
RO
EP3314-0002
Index 1009: Hardware version
Index (hex) Name
Meaning
Data type
Flags
Default
1009:0
Hardware version
Hardware version of the EtherCAT slave
STRING
RO
00
Index 100A: Software version
Index (hex) Name
Meaning
Data type
Flags
Default
100A:0
Software version
Firmware version of the EtherCAT slave
STRING
RO
01