Parameterization and programming
ELX3202 and ELX3204
53
Version: 1.4.0
5.4
ELX32x0 - Object description
Note
EtherCAT XML Device Description
The display matches that of the CoE objects from the EtherCAT XML Device Description.
We recommend downloading the latest XML file from the download area of the
and installing it according to installation instructions.
Note
Parameterization via the CoE list (CAN over EtherCAT)
The terminal is parameterized via the CoE-Online tab (double-click on the respective ob-
ject) or via the Process Data tab (allocation of PDOs). Please note the following general
CoE information when using/manipulating the CoE parameters:
• Keep a startup list if components have to be replaced
• Differentiation between online/offline dictionary, existence of current XML description
• Use
CoE reload
for resetting changes
Note
Relevant objects
The object description refers to the analog input terminals for Pt100 (RTD) in 1 to 4 channel
versions. Observe the indices with regard to the objects relevant for the respective terminal
(channel dependent).
Introduction
The CoE overview contains objects for different intended applications:
• Objects required for parameterization and profile-specific objects required during commissioning
• Objects for indicating internal settings (may be fixed)
The following section first describes the objects required for normal operation, followed by a complete
overview of missing objects.
5.4.1
Objects for commissioning
Index 1011: Restore default parameters
Index
(hex)
Name
Meaning
Data type
Flags
Default
1011:0
Restore default pa-
rameters
Restore default parameters
UINT8
RO
0x01 (1
dec
)
1011:01
SubIndex 01
If this object is set to
0x64616F6C
in the set value
dialog, all backup objects are reset to their delivery
state.
UINT32
RW
0x00000000 (0
dec
)
Index 80n0: RTD settings for 0 ≤ n ≤ 4 (Ch. 1…4)
Note
The filter properties are set only via index 0x8000:15
The filter frequencies are set for all channels of the ELX320x terminals centrally via chan-
nel 1 (index 0x8000:15).