Mounting and wiring
ELX1052, ELX1054 and ELX1058
30
Version: 2.0.0
DIP switch
The DIP switch allows to invert the input signal for each channel of the ELX1054 separately. For the
inversion of the signal, the DIP switch must be set to the ON position.
Fig. 23: ELX1054 - DIP switch
Switch position
for sensor
ON
negative switching
OFF
positive switching (default)
LED display
The following tables are assigned to the respective LED number of a channel.
LED display if
DIP switch
of the associated channel
is in position OFF
(default):
Input LED
Error LED
Meaning
off
on
Error detection: open- circuit on channel (I < 200 µA typ.)
off
off
Usual operation: NAMUR sensor on channel in non-conductive state
("0"; according to IEC 60947-5-6)
on
on
Error detection: short-circuit on channel (I > 6.3 mA typ.)
on
off
Usual operation: NAMUR sensor on channel in conducting state
("1"; according to IEC 60947-5-6)
LED display if
DIP switch
of the associated channel
is in position ON
:
Input LED
Error LED
Meaning
off
on
Error detection: short-circuit on channel (I > 6.3 mA typ.)
off
off
Usual operation: NAMUR sensor on channel in conducting state
("1"; according to IEC 60947-5-6)
on
on
Error detection: open- circuit on channel (I < 200 µA typ.)
on
off
Usual operation: NAMUR sensor on channel in non-conductive state
("0"; according to IEC 60947-5-6)