Product overview

ELX1052, ELX1054 and ELX1058

16

Version: 2.0.0

Technical data for explosion protection ELX1052-0000

ELX1054-0000
ELX1058-0000

Ex marking

II 3 (1) G Ex ec [ia Ga] IIC T4 Gc

II (1) D [Ex ia Da] IIIC

I (M1) [Ex ia Ma] I

Certificate numbers

IECEx BVS 18.0005X

BVS 18 ATEX E 005 X

Power supply

Invariable in connection with ELX9560

Field interfaces

U

O

 = 10.75 V

I

O

 = 12.0 mA

P

O

 = 33 mW

linear

U

O

 = 10.72 V

I

O

 = 10.4 mA

P

O

 = 28 mW

linear

Reactance
(without consideration of the
simultaneousness)

L

0

C

0

L

0

C

0

Ex ia I

100 mH

58 µF

100 mH

58 µF

Ex ia IIA

100 mH

66 µF

100 mH

66 µF

Ex ia IIB

100 mH

15 µF

100 mH

15 µF

Ex ia IIC

100 mH

2.14 µF

100 mH

2.14 µF

Ex ia IIIC 100 mH

15 µF

100 mH

15 µF

2.5

Intended use

 WARNING

Endangering the safety of persons and equipment!

The ELX components may only be used for the purposes described below!

 CAUTION

Observe ATEX and IECEx!

The ELX components may only be used in accordance with the ATEX directive and the IECEx scheme!

The ELX terminals extend the field of application of the Beckhoff bus terminal system with functions for
integrating intrinsically safe field devices from hazardous areas. The intended field of application is data
acquisition and control tasks in discrete and process engineering automation, taking into account explosion
protection requirements.

The ELX terminals are protected by the type of protection "Increased safety" (Ex e) according to
IEC 60079-7 and must only be operated in hazardous areas of Zone 2 or in non-hazardous areas.

The field interfaces of the ELX terminals achieve explosion protection through the type of protection "intrinsic
safety" (Ex i) according to IEC 60079-11. For this reason, only appropriately certified, intrinsically safe
devices may be connected to the ELX terminals. Observe the maximum permissible connection values for
voltages, currents and reactances. Any infringement can damage the ELX terminals and thus eliminate the
explosion protection.

The ELX terminals are open, electrical equipment for installation in lockable cabinets, enclosures or
operating rooms. Make sure that access to the equipment is only possible for authorized personnel.

 CAUTION

Ensure traceability!

The buyer has to ensure the traceability of the device via the Beckhoff Traceability Number (BTN).

Содержание ELX1052

Страница 1: ...Operating manual ELX1052 ELX1054 and ELX1058 Two four and eight channel digital input terminals for NAMUR sensors Ex i 2 0 0 2020 03 09 Version Date...

Страница 2: ......

Страница 3: ...nditions of use for ELX terminals 17 3 2 Installation notes for ELX terminals 17 3 3 Arrangement of ELX terminals within a bus terminal block 19 3 4 Installation position and minimum distances 22 3 5...

Страница 4: ...Table of contents ELX1052 ELX1054 and ELX1058 4 Version 2 0 0...

Страница 5: ...e modification of products that have already been supplied may be made on the basis of the data diagrams and descriptions in this documentation Trademarks Beckhoff TwinCAT EtherCAT EtherCAT G EtherCAT...

Страница 6: ...nded for trained specialists in control automation and drive engineering who are familiar with the applicable national standards Description of instructions In this documentation the following instruc...

Страница 7: ...erminals updated Technical data updated 1 4 0 Chapter Arrangement of ELX terminals at the bus terminal updated 1 3 0 Chapter Installation notes for ELX terminals updated 1 2 0 Chapter Marking of ELX t...

Страница 8: ...nonymous with each revision there is usually a description ESI EtherCAT Slave Information in the form of an XML file which is available for download from the Beckhoff website The revision has been app...

Страница 9: ...minal has a unique Beckhoff Traceability Number BTN Ex marking The Ex marking can be found at the top left on the terminal II 3 1 G Ex ec ia Ga IIC T4 Gc II 1 D Ex ia Da IIIC I M1 Ex ia Ma I IECEx BVS...

Страница 10: ...Foreword ELX1052 ELX1054 and ELX1058 10 Version 2 0 0 Fig 2 ELX9560 0000 with date code 12150000 BTN 000b000 and Ex marking...

Страница 11: ...Foreword ELX1052 ELX1054 and ELX1058 11 Version 2 0 0 Fig 3 ELX9012 with date code 12174444 BTN 0000b0si and Ex marking...

Страница 12: ...minal acquires signals from NAMUR field devices according to EN 60947 5 6 The sensors are supplied with a voltage of 8 2 V and return a diagnosable current signal In this way a wire breakage or short...

Страница 13: ...osable current signal In this way a wire breakage or short circuit can be detected in addition to the switching state The LEDs indicate signal or any error states channel by channel The sensor supply...

Страница 14: ...d records their signals according to IEC 60947 5 6 The sensors are supplied with a voltage of 8 2 V and return a current signal that can be diagnosed In this way in addition to the switching status li...

Страница 15: ...typ 10 mA load typ 15 mA load Electrical isolation 1500 V E Bus field potential Bit width in the process image 2 x 2 bit 4 x 2 bit 4 bit input type NC status 8 x 2 bit Weight approx 45 g approx 50 g...

Страница 16: ...system with functions for integrating intrinsically safe field devices from hazardous areas The intended field of application is data acquisition and control tasks in discrete and process engineering...

Страница 17: ...r removed from the bus terminal system if all supply voltages have been switched off or if a non explosive atmosphere is ensured The connections of the ELX9560 power supply terminal may only be connec...

Страница 18: ...housing e g through the ventilation slots in the housing Use only the openings provided in the housing front and appropriate tools to actuate the spring loaded terminal contacts on the front side for...

Страница 19: ...ted to the right of an ELX9560 nor to the left of any ELX signal terminal The last terminal of each ELX segment is to be covered by an ELX9012 bus end cover unless two ELX9410 power supply terminals a...

Страница 20: ...0 power supply terminal Fig 11 Invalid arrangement missing ELX9560 power supply terminal Fig 12 Invalid arrangement terminal that does not belong to the ELX series within the ELX terminal segment Fig...

Страница 21: ...ELX9560 When configuring the ELX terminal segment please note the maximum available output current of the ELX9560 power supply terminal in accordance with the specified technical data If required an...

Страница 22: ...lectronics through convection The direction indication down corresponds to the direction of positive acceleration due to gravity Minimum distances Observe the following minimum distances to ensure opt...

Страница 23: ...re 1 First attach the fieldbus coupler to the mounting rail 2 The bus terminals are now attached on the right hand side of the fieldbus coupler Join the compo nents with tongue and groove and push the...

Страница 24: ...ections within a bus terminal block The electric connections between the Bus Coupler and the Bus Terminals are automatically realized by joining the components The six spring contacts of the E Bus dea...

Страница 25: ...st and simple assembly High Density Terminals HD Terminals Fig 19 High Density Terminals The Bus Terminals from these series with 16 connection points are distinguished by a particularly compact desig...

Страница 26: ...the screwdriver or move it alternately don t toggle 2 The wire can now be inserted into the round terminal opening without any force 3 The terminal point closes automatically when the pressure is rel...

Страница 27: ...ne wire per terminal point When using fine wire conductors it is recommended to connect them with wire end sleeves in order to establish a safe conductive connection In addition make sure that the pin...

Страница 28: ...not implemented 7 not implemented Uv2 8 Sensor supply Channel 2 LED Display The following table is assigned to the respective LED number of a channel Input LED Error LED Meaning off on Error detection...

Страница 29: ...ig 22 ELX1054 Contact assignment Terminal point Description Designation No Input 1 1 Input Channel 1 Uv1 2 Sensor supply Channel 1 Uv3 3 Sensor supply Channel 3 Input 3 4 Input Channel 3 Input 2 5 Inp...

Страница 30: ...Meaning off on Error detection open circuit on channel I 200 A typ off off Usual operation NAMUR sensor on channel in non conductive state 0 according to IEC 60947 5 6 on on Error detection short cir...

Страница 31: ...t channel 2 Input 3 3 Input channel 3 Input 4 4 Input channel 4 Input 5 5 Input channel 5 Input 6 6 Input channel 6 Input 7 7 Input channel 7 Input 8 8 Input channel 8 Uv1 9 Sensor supply channel 1 Uv...

Страница 32: ...on channel I 200 A typ off off Usual operation NAMUR sensor on channel in non conductive state 0 according to IEC 60947 5 6 on on Error detection short circuit on channel I 6 3 mA typ on off Usual ope...

Страница 33: ...this kind of certification are marked by this sign 2 UL certification according to UL508 with limited power consumption The current consumed by the de vice is limited to a max possible current consum...

Страница 34: ...of the ELX series may only be used in potentially explosive areas of Class I Division 2 Group A B C D or in non explosive areas WARNING Consider the Control Drawing ELX documentation When installing t...

Страница 35: ...or Beckhoff components there Beckhoff Headquarters Beckhoff Automation GmbH Co KG Huelshorstweg 20 33415 Verl Germany Phone 49 5246 963 0 Fax 49 5246 963 198 e mail info beckhoff com Beckhoff Support...

Страница 36: ...segment and two ELX9410 at the end of the ELX terminal segment 19 Fig 9 Valid arrangement multiple power supplies by ELX9560 each with an upstream ELX9410 19 Fig 10 Valid arrangement ELX9410 in front...

Отзывы: