![Beckhoff EL922 Series Скачать руководство пользователя страница 135](http://html1.mh-extra.com/html/beckhoff/el922-series/el922-series_documentation_2719614135.webp)
Commissioning
EL922x
135
Version: 1.0
7.6.3.6
Output data
0x00 (0
dec
)Index 70n0 Inputs (for n = 0, Ch.1; n = 1, Ch. 2)
Index (hex) Name
Meaning
Data type
Flags
Default
70n0:0
Inputs
Max. Subindex
UINT8
RO
0x02 (2
dec
)
70n0:01
Control__Reset
Reset channel
BOOLEAN
RO
0x00 (0
dec
)
70n0:02
Control__Switch
Connect channel
BOOLEAN
RO
0x00 (0
dec
)
7.6.3.7
Information and diagnostic data
Index 10F3 Diagnosis History
Index (hex) Name
Meaning
Data type
Flags
Default
10F3:0
Diagnosis History
Maximum subindex
UINT8
RO
0x15 (21
dec
)
10F3:01
Maximum Messages
Maximum number of stored messages. A maximum
of 50 messages can be stored
UINT8
RO
0x00 (0
dec
)
10F3:02
Newest Message
Subindex of the latest message
UINT8
RO
0x00 (0
dec
)
10F3:03
Newest Acknowl-
edged Message
Subindex of the last confirmed message
UINT8
RW
0x00 (0
dec
)
10F3:04
New Messages Avail-
able
Indicates that a new message is available
BOOLEAN
RO
0x00 (0
dec
)
10F3:05
Flags
not used
UINT16
RW
0x0000 (0
dec
)
10F3:06
Diagnosis Message
001
Message 1
OCTET-
STRING[20]
RO
{0}
...
...
...
...
...
...
10F3:15
Diagnosis Message
016
Message 16
OCTET-
STRING[20]
RO
{0}
Index 10F8 Actual Time Stamp
Index (hex) Name
Meaning
Data type
Flags
Default
10F8:0
Actual Time Stamp
Time stamp
UINT64
RO
Index 90n0 Info Data (for n = 0, Ch.1; n = 1, Ch. 2)
Index (hex) Name
Meaning
Data type
Flags
Default
90n0:0
Info Data
Max. Subindex
UINT8
RO
0x17 (23
dec
)
90n0:11
Tripped Counter Short
Circuit
Trip counter short circuit (≥1.5 x I
N
)
UINT32
RO
0x00000000 (0
dec
)
90n0:12
Tripped Counter
Overload
Trip counter overload (≥1.1 x I
N
)
UINT32
RO
0x00000000 (0
dec
)
90n0:13
Tripped Counter
Hardware Protection
Trip counter hardware protection
UINT32
RO
0x00000000 (0
dec
)
90n0:14
Tripped Counter
Overvoltage
Trip counter overvoltage (≥ 32 V DC)
UINT32
RO
0x00000000 (0
dec
)
90n0:15
Tripped Counter Un-
dervoltage
Trip counter undervoltage
UINT32
RO
0x00000000 (0
dec
)
90n0:16
Remaining Cool
Down Time
Remaining restart time (cooling time)
UINT16
RO
0x0000 (0
dec
)
90n0:17
Max Current Drag In-
dicator
Current drag indicator: Maximum current flow in 0.01
A
UINT16
RO