EL7211-901x, EL7221-901x
Fig. 42: EL7211-901x, EL7221-901x - LEDs
LEDs
LED
Color
Meaning
RUN
green
This LED indicates the terminal's operating state:
off
State of the EtherCAT State Machine:
INIT
= initialization of the terminal
flashing
rapidly
State of the EtherCAT State Machine:
BOOTSTRAP
flashing
State of the EtherCAT State Machine:
PREOP
= function for mailbox communication and
different standard-settings set
Single flash State of the EtherCAT State Machine:
SAFEOP
= verification of the Sync Manager chan-
nels and the distributed clocks.
Outputs remain in safe state
on
State of the EtherCAT State Machine:
OP
= normal operating state; mailbox and process
data communication is possible
Drive OK
green
on
Driver stage ready for operation
Limit
orange
on
The LED is linked with bit 11 of the status word (
limit active)
Limit reached (e.g. torque or speed limit)
Read OCT
green
flashing
The electronic type plate is being read
off
The reading of the electronic type plate has been completed
Warning
orange
flashing
Error while reading the type plate
on
The LED is linked with bit 7 of the status word (
) (warning)
The “Warning” threshold value is exceeded.
I²T model
Voltage missing at STO input
Temperature (80°C) exceeded
Voltage
Enable
green
on
The LED is linked with the bits 1 and 2 of status word (
"Switched on" or "Operation enabled")
Driver stage enabled
Error
red
on
The LED is linked with bit 3 of the status word (
) (fault)
The “Error” threshold value is exceeded.
Overcurrent
STO triggered with active axis
Voltage not available
Resolver not connected
Max. temperature (100°C) exceeded
+24 V via power
contacts
green
on
24 V voltage supply for the terminal is present.
DC link supply
green
on
Voltage for the DC link supply is present.
Содержание EL72 1-901 Series
Страница 1: ...Documentation EL72x1 901x Servo Motor Terminals with OCT and STO 50 V DC 1 9 2020 02 18 Version Date...
Страница 2: ......
Страница 6: ...Table of contents EL72x1 901x 6 Version 1 9...
Страница 20: ...Product overview EL72x1 901x 20 Version 1 9 2 3 Technical data...
Страница 49: ...Installation EL72x1 901x 49 Version 1 9 Fig 36 Shield busbar Fig 37 Shield busbar clamp...
Страница 86: ...Commissioning EL72x1 901x 86 Version 1 9 Fig 88 Incorrect driver settings for the Ethernet port...
Страница 140: ...Commissioning EL72x1 901x 140 Version 1 9 0hex 80hex Fault reset 6hex Shutdown 7hex Switch on Fhex Enable operation...
Страница 141: ...Commissioning EL72x1 901x 141 Version 1 9 Fig 176 DS402 State Machine...
Страница 150: ...Commissioning EL72x1 901x 150 Version 1 9 Fig 184 Touch Probe inputs...
Страница 172: ...Commissioning EL72x1 901x 172 Version 1 9 Fig 207 Process Data tab SM2 EL72x1 0010 default...
Страница 256: ...Appendix EL72x1 901x 256 Version 1 9 9 5 Certificates Fig 233 EL72x1 9014_Certificate...