Installation
EL6652-00x0
31
Version: 2.5
4.4
Positioning of passive Terminals
Hint for positioning of passive terminals in the bus terminal block
EtherCAT Terminals (ELxxxx / ESxxxx), which do not take an active part in data transfer within the
bus terminal block are so called passive terminals. The passive terminals have no current consump-
tion out of the E-Bus.
To ensure an optimal data transfer, you must not directly string together more than 2 passive termi-
nals!
Examples for positioning of passive terminals (highlighted)
Fig. 20: Correct positioning
Fig. 21: Incorrect positioning
4.5
Installation positions
NOTE
Constraints regarding installation position and operating temperature range
Please refer to the technical data for a terminal to ascertain whether any restrictions regarding the installa-
tion position and/or the operating temperature range have been specified. When installing high power dissi-
pation terminals ensure that an adequate spacing is maintained between other components above and be-
low the terminal in order to guarantee adequate ventilation!
Содержание EL6652-00 0 Series
Страница 1: ...Documentation EL6652 00x0 EtherNet IP Master Slave EtherCAT Terminal 2 5 2019 10 22 Version Date ...
Страница 2: ......
Страница 63: ...Commissioning EL6652 00x0 63 Version 2 5 Fig 68 Incorrect driver settings for the Ethernet port ...
Страница 102: ...Commissioning EL6652 00x0 102 Version 2 5 Fig 131 Diagnosis of ECatState and State ...
Страница 117: ...Commissioning EL6652 00x0 117 Version 2 5 Fig 144 Creating a new controller Append a new module ...
Страница 118: ...Commissioning EL6652 00x0 118 Version 2 5 Fig 145 Appending a new module Select ETHERNET MODULE Generic Ethernet Module ...
Страница 120: ...Commissioning EL6652 00x0 120 Version 2 5 Fig 147 Transferring the parameters into the New Modules mask ...