Basics communication
EL6652-00x0
19
Version: 2.5
Fig. 13:
EtherCAT tab -> Advanced Settings -> Behavior -> Watchdog
Notes:
• the multiplier is valid for both watchdogs.
• each watchdog has its own timer setting, the outcome of this in summary with the multiplier is a
resulting time.
• Important: the multiplier/timer setting is only loaded into the slave at the start up, if the checkbox is
activated.
If the checkbox is not activated, nothing is downloaded and the ESC settings remain unchanged.
Multiplier
Multiplier
Both watchdogs receive their pulses from the local terminal cycle, divided by the watchdog multiplier:
1/25 MHz * (watchdog mult 2) = 100 µs (for default setting of 2498 for the multiplier)
The standard setting of 1000 for the SM watchdog corresponds to a release time of 100 ms.
The value in mult 2 corresponds to the number of basic 40 ns ticks representing a watchdog tick.
The multiplier can be modified in order to adjust the watchdog time over a larger range.
Содержание EL6652-00 0 Series
Страница 1: ...Documentation EL6652 00x0 EtherNet IP Master Slave EtherCAT Terminal 2 5 2019 10 22 Version Date ...
Страница 2: ......
Страница 63: ...Commissioning EL6652 00x0 63 Version 2 5 Fig 68 Incorrect driver settings for the Ethernet port ...
Страница 102: ...Commissioning EL6652 00x0 102 Version 2 5 Fig 131 Diagnosis of ECatState and State ...
Страница 117: ...Commissioning EL6652 00x0 117 Version 2 5 Fig 144 Creating a new controller Append a new module ...
Страница 118: ...Commissioning EL6652 00x0 118 Version 2 5 Fig 145 Appending a new module Select ETHERNET MODULE Generic Ethernet Module ...
Страница 120: ...Commissioning EL6652 00x0 120 Version 2 5 Fig 147 Transferring the parameters into the New Modules mask ...