Product overview
EL6652-00x0
16
Version: 2.5
2.2
EL6652-0000, EL6652-0010 - Technical data
Technical data
EL6652
EL6652-0010
Description
Master (Scanner)
Slave
Number of possible slave devices
16 slaves
-
Number of ports/channels
2 (switched)
Ethernet interface
100 MB Ethernet with 2 x RJ45
Data width
max. 1 kByte input and 1 kByte output data
Cable length
up to 100 m Twisted-Pair
Hardware diagnosis
Status LEDs
Housing
24 mm housing
Power supply
via the E-Bus
Current consumption from E-Bus
typ. 400 mA
Electrical isolation
500 V (E-Bus/Ethernet)
Configuration
via TwinCAT System Manager
- from TwinCAT 2.11 Build 2248
- from TwinCAT 3.1 Build 4018.5
Weight
ca. 75 g
Permissible relative humidity
95%, no condensation
Dimensions (W x H x D)
approx. 24 mm x 100 mm x 70 mm
on 35 mm mounting rail according to EN 60715
Vibrations- / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
Permissible ambient temperature
range during operation
- 0°C ... +55°C (
aligned in horizontal installation position [
- 0°C ... +45°C (
all other installation positions [
Permissible ambient temperature
range during storage
-25°C ... + 85°C
Protection class
IP20
Installation position
variable, see
!
Approval
CE
Содержание EL6652-00 0 Series
Страница 1: ...Documentation EL6652 00x0 EtherNet IP Master Slave EtherCAT Terminal 2 5 2019 10 22 Version Date ...
Страница 2: ......
Страница 63: ...Commissioning EL6652 00x0 63 Version 2 5 Fig 68 Incorrect driver settings for the Ethernet port ...
Страница 102: ...Commissioning EL6652 00x0 102 Version 2 5 Fig 131 Diagnosis of ECatState and State ...
Страница 117: ...Commissioning EL6652 00x0 117 Version 2 5 Fig 144 Creating a new controller Append a new module ...
Страница 118: ...Commissioning EL6652 00x0 118 Version 2 5 Fig 145 Appending a new module Select ETHERNET MODULE Generic Ethernet Module ...
Страница 120: ...Commissioning EL6652 00x0 120 Version 2 5 Fig 147 Transferring the parameters into the New Modules mask ...